Setting of user parameters
The TCY-BH-U can be adapted to fit perfectly into your application. The control operation is defined by parameters. The
parameters are set during operation by using the control buttons.
The parameters may only be accessed by entering a code. There are two levels of parameters: User operation parameters for
access control settings, and Expert parameters for control functions and unit setup. The codes for user levels and expert
levels are different. Only control experts should be given the control parameter code.
The parameters can be changed as follows:
1.
Press UP and DOWN button simultaneously for three seconds. The display shows the software version in the large
digits and the product code in the small digits.
2.
Pressing the OPTION button will indicate CODE on the small digits and 000 on the large digits.
3.
The code for accessing the user parameters is 009
4.
Select this using UP or DOWN buttons.
5.
Press OPTION button after selecting the correct code.
6.
Once logged in, the parameter is displayed immediately.
7.
Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the OPTION button. Three
triangles will show up on the lower right and indicate that the parameter may be modified now. Use UP or DOWN
buttons to adjust the value.
8.
After you are done, press OPTION or POWER in order to return to the parameter selection level.
9.
Press the POWER button again so as to leave the menu. The unit will return to normal operation if no button is
pressed for more than 5 minutes.
User Parameters
Parameter
Description
UP 00
Enable change of operation modes
UP 01
Enable change of setpoints
UP 02
Enable access to Time programs
UP 03
State after power failure:
0 = Switched OFF, 1 = Switched ON, 2 = state before power failure
UP 04
Enable Economy functionality
UP 05
Celsius or Fahrenheit, Select ON for Fahrenheit, OFF for Celsius
UP 06
Select contents of small digits in standard mode:
00 = OFF
01 = Setpoint
02 = Humidity Sensor
03 = External Temperature Sensor
04 = Clock
UP 07
Clock display type:
Deluxe only
OFF = Show 24hour clock
ON = Show 12hour clock (AM, PM)
UP 08
Reset timer for override mode: Only available for deluxe version
Deluxe only
0
= Reset of override mode is not active.
1...255 = delay in minutes to switch off device if ON/Economy
mode is activated while the unit is scheduled to be in OFF
mode
Doc:70-07-0102, V1.1, Date: 20100504
Subject to alteration
© Vector Controls GmbH, Switzerland
Humidistat TCY-BH-U
Setting Range
Factory Setting
ON, OFF
ON, OFF
ON, OFF
0, 1, 2
ON, OFF
OFF (Disabled)
ON, OFF
OFF (Celsius)
0...5
ON, OFF
0...255
ON (Enabled)
ON (Enabled)
ON (Enabled)
2
04 Deluxe:
show clock
01 Standard:
show setpoint
OFF (24h)
60 (Min)