Connection Terminals; Mechanical Design And Installation - Vector TCY-BH-U Manual

Intelligent humidistat
Hide thumbs Also See for TCY-BH-U:
Table of Contents

Advertisement

Connection terminals

TCY-BH-U
1
2
3
4 5 6 7 8

Mechanical Design and installation

The unit consists of two parts: (a) The power case with attached mounting plate and (b) the front part.
Mounting location
On an easy accessible interior wall, approx. 1.5 m (4.5') above the floor in an area of average temperature.
Avoid exposure to direct sunlight or other heat sources, e.g. the area above radiators and heat emitting electrical
equipment.
Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.
Location of mounting is less critical if external temperature sensors are used
Installation
1.
Connect the wires to be connected to the terminals of the power case according to wiring diagram
2.
Install the mounting plate to the flush mounting box. Make sure that the nipple with the front retaining screw is at
the bottom. Make sure the mounting screw heads do not stand out more than 5 mm (0.2") from the surface of the
mounting plate.
3.
Ensure that the jumpers are set correctly.
4.
Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.
5.
Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle way
until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is normal.
Do not use excessive force!
6.
With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to the
mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the screw too
much.
Doc:70-07-0102, V1.1, Date: 20100504
Subject to alteration
Terminal-description:
1.
Connection for power-supply (24 V AC/DC, ±10%). In case of DC,
connect the negative power-terminal. Common connection for analog in- and
outputs.
2.
Connection for power-supply (24 V AC/DC, ±10%). In case of DC,
connect the positive power-terminal
3.
Switched contact "DO 1" Humidify or Fan (Max. 2 (1.2A)
4.
Switched contact "DO 1" Humidify or Fan (Max. 2 (1.2A)
5.
Switched contact "DO 2" Dehumidify or Fan (Max. 2 (1.2A)
6.
Switched contact "DO 2" Dehumidify or Fan (Max. 2 (1.2A)
7.
Thermistor input "RT" (Thermistor Sxx-Tn10)
8.
Thermistor input "RT" (Thermistor Sxx-Tn10)
© Vector Controls GmbH, Switzerland
Humidistat TCY-BH-U