LG APUW100LFT0 Installation Manual page 31

Floor standing
Table of Contents

Advertisement

Error
Description
Code
21
DC Peak (IPM fault) Error
22
CT2 Error (Input of Over-Current)
23
DC Link Error (High/Low DC Voltage)
26
DC Comp Position Detection Error
27
PSC/PFC Over-Current Error (HW)
29
Comp Phase Over-Current Error
32
Discharge Pipe Overheating Error (INV Comp)
35
Low Pressure Drop
41
Discharge Pipe Sensor Error (INV Comp)
43
Pressure Sensor Error
44
Air Sensor Error
45
Cond. Mid-pipe sensor error
46
Suction Pipe Sensor Error
48
Cond. Out-Pipe Sensor Error
51
Over-Capacity Connection Error
52
Communication Error between Main PCB Inverter PCB
53
Communication Error between Outdoor Device Indoor Device
54
Open and Reverse Phase Error
60
EEPROM Check Sum Error
61
Outdoor Device Pipe Overheating Error
62
Heat-sink Overheating Error
65
Heat-sink Sensor Error
Outdoor BLDC Fan Lock Error
67
refer to Outdoor fan PCBA Error Table
73
PSC/PFC Over-Current Error (SW)
SELF-DIAGNOSIS FUNCTION
Error Display
7 segment Red LED Green LED
2 times ◑ 1 time ◑ 10 times within 1h
CH 21
2 times ◑ 2 times ◑
CH 22
2 times ◑ 3 times ◑
CH 23
2 times ◑ 6 times ◑ 10 times within 1h
CH 26
2 times ◑ 7 times ◑ 10 times within 1h
CH 27
2 times ◑ 9 times ◑ 10 times within 1h
CH 29
3 times ◑ 2 times ◑
CH 32
3 times ◑ 5 times ◑
CH 35
4 times ◑ 1 time ◑
CH 41
4 times ◑ 3 times ◑
CH 43
4 times ◑ 4 times ◑
CH 44
4 times ◑ 5 times ◑
CH 45
4 times ◑ 6 times ◑
CH 46
4 times ◑ 8 times ◑
CH 48
5 times ◑ 1 time ◑
CH 51
5 times ◑ 2 times ◑
CH 52
5 times ◑ 3 times ◑
CH 53
5 times ◑ 4 times ◑
CH 54
6 times ◑
CH 60
-
6 times ◑ 1 time ◑
CH 61
6 times ◑ 2 times ◑
CH 62
6 times ◑ 5 times ◑
CH 65
6 times ◑ 7 times ◑ 10 times within 1h
CH 67
7 times ◑ 3 times ◑
CH 73
31
Operation
Count
State
Stop
Infinite restart
Stop
Infinite restart
Stop
Stop
Stop
Stop
Infinite restart
Stop
Infinite restart
Stop
1 time within 1h
Stop
1 time within 1h
Stop
1 time within 1h
Stop
1 time within 1h
Stop
1 time within 1h
Stop
1 time within 1h
Stop
1 time within 1h
Stop
1 time within 1h
Stop
1 time within 1h
Stop
1 time within 1h
Stop
1 time within 1h
Stop
Infinite restart
Stop
Infinite restart
Stop
1 time within 1h
Stop
Stop
Infinite restart
Stop

Hide quick links: