Internal Use Only
http://biz.lgservice.com
Floor Standing Type Air Conditioner
SVC MANUAL
MODEL : AP-Z Series
CAUTION
Before Servicing the unit, read the safety precautions in General SVC manual.
Only for authorized service personnel.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AP-Z Series and is the answer not in the manual?

Questions and answers

Summary of Contents for LG AP-Z Series

  • Page 1 Internal Use Only http://biz.lgservice.com Floor Standing Type Air Conditioner SVC MANUAL MODEL : AP-Z Series CAUTION Before Servicing the unit, read the safety precautions in General SVC manual. Only for authorized service personnel.
  • Page 2: Table Of Contents

    Installation of Indoor, Outdoor Unit.......................23 Test running.............................29 3-way valve ..............................31 Cycle Troubleshooting Guide .......................37 Electronic Parts Troubleshooting Guide ....................38 Exploded View............................41 - 2 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 3: Safety Precautions

    • There is risk of fire or electric • There is risk of fire or electric cause fire or electric shock shock. shock. - 3 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 4 • There is risk of fire or electric • There is risk of fire, failure of the shock. shock. product, or electric shock. - 4 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 5 • Low refrigerant levels may cause failure of product. • A bad connection may cause water leakage. - 5 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 6 • There is risk of personal injury and failure of product. • There are sharp and moving parts that could cause personal injury. - 6 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 7: Functions

    • Used to circulate room air without cooling. AutoRestart • The power comes on again after a power failure. - 7 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 8: Remote Control

    Room Temperature Control • Up: up to 30°C • Down: down to 16°C Indoor Fan speed control • High, Low - 8 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 9 • De-ice PCB Outdoor Fan Speed Control • One speed Sensing Heat Exchanger Temperature • Heat exchanger temperature sensor (Thermistor) - 9 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 10: Product Specifications

    198.4 (90) 330.7 (150) Liquid 3/8 (9.52) 3/8 (9.52) 5/8 (15.88) Connections Inch(mm) 5/8 (15.88) 3/4 (19.05) 1 (25.4) - 10 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 11 Outdoor Unit Air Outlet Vent Air Intake Vent (Rear) Remote Signal Receptor Air Outlet Vent Air Intake Vent Piping - 11 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 12: Wiring Diagram

    3854A20144Z CAPACITOR(COMP) KEY PCB ASM DOOR SENSOR (OPTION SENSOR) C TH THERMISTOR(COND TH) L/DOOR L/DOOR MOTOR MOTOR TERMINAL BLOCK - 12 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 13 Wiring Diagram ■ INDOOR *AP-Z286R20, AP-Z286R30 ■ OUTDOOR *AP-Z286RC0, AP-Z286R20, AP-Z286R30 - 13 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 14: Outdoor Unit Wiring Diagram

    POWER SUPPLY HEATER 3Ø,380-415V~,50Hz T/B2 TERMINAL(4P) YL BK YL BK (T1) (T2) (T3) 20SV 49FMo 49FMo GN/YL P/NO : 3854A20119V - 14 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 15 THERMISTOR FOR PIPE TEMP.(OUTDOOR) MAIN TERMINAL BLOCK 49FMo INTERNAL T.P FOR FMo 20SV REVERSING COIL TERMINAL BLOCK FOR CONNECTING - 15 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 16: Operation Details

    ', the Off-Timer function will be cancelled. - During Off-Timer Operation, if you repress the timer set button, the rest time will be displayed. - 16 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 17: Heating Mode Operation

    Selecting speed ≥ 39°C Ⅳ ≥28。 C Selecting speed > 34°C Ⅴ ≥26。 C ≤ 34°C Ⅵ ≤26。 C - 17 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 18 Indoor fan speed Pipe temp. Ⅰ ≤22°C(Hot start operating) Ⅱ ≥22°C Ⅲ Selecting speed ≥C°C Ⅳ ≤D°C Ⅴ ≤20°C - 18 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 19 Defrost Outdoor Pipe Temp. Defrost 12°C (Defrost OFF) -6°C (Defrost ON) HOT- START Indoor Fan Compressor 4-Way Valve - 19 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 20 ❈ During this function is operating, any buttons of Display Panel don't work. But it is possible to operate with Remote controller. - 20 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 21 In case the power comes on again after a power failure, Auto Restarting Operation is the function to operate pro- cedures automatically to the previous operating conditions. - 21 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 22 - After 18 ± 1 minutes of operation, it becomes off itself. - During the operation, signal 88 stands for "Lo" - 22 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 23: Installation Of Indoor, Outdoor Unit

    A (m) B (m) GAS SIDE LIQUID SIDE 5/8" 1/4" 28K/30K 5/8" 3/8" Outdoor unit 5/8" 3/8" 11/10" 1/2" - 23 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 24: Indoor Unit Installation

    Tilt Cut if necessary More than 15mm ④ Cut the extruded outside part of the plastic tube, if necessary. - 24 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 25: Installation Method

    Connecting the cable between outdoor Preparation of the operating and indoor unit Connecting the main cable to outdoor unit - 25 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 26: Preparation Of Installation Parts And Tools

    To connect the cable from outdoor unit to indoor unit Drain hose sockets, elbows To remote the condensing water - 26 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 27: Preparation Of Piping

    Cone Copper pipe Clamp handle Red arrow mark = Improper flaring = Inclined Surface Cracked Uneven damaged thickness - 27 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 28: Connection Of Piping

    ③ Keep in mind that the bending part should not be cracked and make the radius (R) as long as possi- ble (Refer to Fig. 2)` (Fig. 2) - 28 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 29: Test Running

    2. Ensure the difference between the intake temperature and the discharge one is more than 8°C (Cooling) or reversely (Heating). - 29 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 30: Hand Over

    HAND OVER Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.). - 30 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 31: 3-Way Valve

    (5) Set the liquid side valve to the closed posi- tion. - 31 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 32 – Close the valve on the gas cylinder and dis- charge the refrigerant until the gauge indicates 3 to 5 kg/cm - 32 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 33 – Discharge the refrigerant gradually; if it is dis- charged too suddenly, the refrigeration oil will also be discharged. - 33 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 34 (4) Disconnect the charge hose from the vacuum pump. – Vacuum pump oil. If the vacuum pump oil becomes dirty or depleted, replenish as needed. - 34 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 35: Gas Charging

    1 minute and then repeat the procedure (pumping down-pin). - 35 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 36 - Be sure to check gas leakage. mately 1 minute and then repeat the procedure (pumping down-pin). - 36 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 37: Cycle Troubleshooting Guide

    2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty. - 37 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 38: Electronic Parts Troubleshooting Guide

    Is IC03M operated Exchange IC03M normally? Is the each Relay Exchange Relay any problem? Check the fan motor and connector. (CN-MOTOR) - 38 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 39 Is the AC220V (AC 240 V) between connector(CN-outunit) Replacement RY-COMP ① and ③ of Main P.C.B Check the wiring diagram. - 39 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 40 Is the AC220V (AC 240 V) between Replacement RY-HEATER connector(HEATER) and CN-outunit ① of Main P.C.B Check the heater wiring - 40 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 41: Exploded View

    235512 146811C 268711A 267110 437210A W0CZZA W0FZZ W6640A W6640B 249941 268711B 135313B 268711C 159830C 249951 135303B 237201 135313A 135303A - 41 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 42 159830A 35211C 266000 336600 266000 352150 130911 W4811A 159830B 349600 567480B 266090 336610 W50400 349480A 346810 730700 140570 359012 - 42 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 43 Exploded View 2. Outdoor Unit - 43 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 44 1. Indoor Unit 135310 753000 267110 146812 753010 137211 268714 W4811 668713 W4810 354210 237202 354210 W4810 263230-1 330870 152302 135313 - 44 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 45 Exploded View 135515 249951 249941 268715 W4810 135500 130900 W0CZZ W50400 359012 336610 346810 349480 W4810 135317 150170 349600 130400 - 45 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 46 Exploded View 2. Outdoor Unit - 46 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 47 330720 359012 135316 147901A 336610A 147911 359012 330720 147901B W0CZZA 159830 336610B 249941A 249951 135313B 268711B 135313A 268711D 249941B - 47 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 48 135515 137213G 137213C 137213F 137213A 346810 150170 137213B 354210 352118 137213E 437212 137213D W4810 352115 130400 W4811 330871 730700 - 48 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 49 Remark Compressor 2520UUCY2AA 554160A Barrier Side Harness,Multi 6631A20033E W6631A APUZ728FA0 Heating Compressor 2520UBAY2AA 554160B Service Valve Harness,Multi 6631A20033F W6631B - 49 - Copyright ©2010 LG Electronics. Inc. All right reserved. LGE Internal Use Only Only for training and service purposes...
  • Page 50 FEBRUARY, 2010 P/NO : 3828A20156G...