Webster JBE Series Operation, Maintenance & Installation Manual page 20

Forced draft burners, high swirl combustion head
Table of Contents

Advertisement

The burner must be level.
Figure C-4
Typical #2 Oil Field Piping
Check Valve
(See Note)
JBE(X) Manual
This surface must be
sealed against the vessel.
Check vessel mounting
requirements.
Tighten clamp bolts
uniformly - check after
firing for several hours.
Figure C-3
Burner Mounting Instruction
Vacuum
Shutoff Valve
Gauge
Strainer
Supply to Pump
Shutoff Valve
Return to Tank
Fuel Oil Tank
Page 20
Refractory
Front Plate
Attachment to vessel varies with manufacturer
(follow vessel manufacturers recommendation.
The gas piping from the burner to the train
should have as few elbows as possible to
reduce pressure drop.
Burner
Oil Pressure
Regulator
Oil Pump
Note: Location of check valve
varies with system. Check valve
is usually located as close as
possible to tank outlet.
Fill voids
between front
plate and
vessel with
ceramic blanket
4" deep or as
defined by
vessel
manufacturer.
Entire O.D. of
refractory should
be covered.
Fiberglass rope gasket
must be coiled to
cover the full mounting
flange surface.
Section C - Installation

Advertisement

Table of Contents
loading

This manual is also suitable for:

Jbex series

Table of Contents