3.0

Precautions

3.1

Installation Precautions (General)

1) Install the unit in a well-ventilated location; allow at least 10 cm (4
inches) on all sides for air ventilation and for maintenance.
2) Install the unit where the ambient is within the correct operation range
(see Specifications Section 4.0).
3) Do not allow liquids or foreign objects to get inside the UPS.
4) Do not install the UPS in a location that is subject to high humidity. Also,
do not install the unit in areas that are exposed to direct sunlight, or
contaminated areas subject to high levels of airborne dust, metal particles,
or flammable gas.
Ambient temperature range for operating the UPS is 0° to 40°C (32° ~ 104°F);
25°C (77°F) is the recommended operating temperature for maximum
battery life.
5) Avoid installation near sources of electrical noise. Always make sure that
the unit's ground is intact to prevent electrical shock and help prevent
electrical noise.
6) This UPS generates and radiates radio-frequency energy during operation.
Although RFI noise filters are installed inside the unit, there is no guarantee
that the UPS will not influence some sensitive devices, which are operating
in near proximity. If such interference occurs, the UPS should either be
installed farther away from the affected equipment and/or powered from a
different source than the affected equipment.
3.2

Installation Precautions (Rack mounted)

1) Install the UPS in a conventional rack-style structure. The recommended
rack slide for the BLACK GOLD TB series UPS is General Devices, CTS-
124 (Call Toshiba for further information on rack slides). The rack must
be bolted to the floor, secured permanently to a wall, or otherwise
secured to prevent toppling.
2) Allow at least 4 inches of open space in the front and rear of the unit for
proper ventilation. Allow at least 6 inches of open space at the rear of
the unit for operation and disconnect devices.
3) Two people handling is required when moving this unit into and out of the
rack structure.
TOSHIBA
Front Panel Cutout
CAUTION
10
Use both handles when lifting entire
weight of the unit, unit weight
119.00lbs. (53.98 kg.) for the 120Vac
111.00lbs. (50.35 kg.) for the 230Vac