Page 2
All rights reserved. The information in this document is subject to change without notice. Publish statement Thank you for purchasing this series UPS. This series UPS is an intelligent, single phase in single phase out, high frequency online UPS designed by our R&D team who is with years of designing experiences on UPS.
1.Safety Important safety instructions – Save these instructions There exists dangerous voltage and high temperature inside the UPS. During the installation, operation and maintenance, please abide the local safety instructions and relative laws, otherwise it will result in personnel injury or equipment damage. Safety instructions in this manual act as a supplementary for the local safety instructions.
2.Main Features 2.1 Summarization This series UPS is a kind of single phase in single phase out high frequency online UPS, it provides two capacities: The 6kVA and 10kVA. The products are modularized and adopt the N+X redundancy. It can flexibly increase the number of the UPS modules according to the load capacity which is convenient for flexible allocation and gradually investment.
3.Installation 3.1 Unpack checking 1. Don’t lean the UPS when moving it out from the packaging 2. Check the appearance to see if the UPS is damaged or not during the transportation, do not switch on the UPS if any damage found. Please contact the dealer right away. 3.
3.4 Installation notes ◆Please place the UPS in a clean, stable environment, avoid the vibration, dust, humidity, flammable gas and liquid, corrosive objects. To avoid from high room temperature, a system of room extractor fans is recommended to be installed. Optional air filters are available if the UPS operates in a dusty environment.
UPS Output ◆ Any external distribution board used for load distribution shall be fitted with protective devices that may avoid the risk of UPS overloaded. Over-current ◆ Protection device shall be installed at the distribution panel of the incoming main supply.
3.7 Power cable connect Once the equipment has been finally positioned and secured, connect the power cables as described in the following procedure. Verify the UPS is totally isolated from its external power source and also all power isolators of the UPS are open. Check to see if they are electrically isolated, and post any necessary warning signs to prevent their inadvertent operation .
Note: The BAT+ of the UPS connect poles is connected to the anode of the positive battery, the BAT- is connected to the cathode of the positive battery and the anode of the negative battery, the BAT- is connected to the cathode of the negative battery。...
3.9.1 Cabinet installation Connect all the UPSes needed to be put into parallel system as below picture. Make sure each UPS input breaker is in “off” position and there is no any output from each UPS connected. Battery groups can be connected separately or in parallel, which means the system itself provides both separate battery and comman battery.
3.9.3 Requirement for the parallel system A group of paralleled modules behave as one large UPS system but with the advantage of presenting higher reliability. In order to assure that all modules are equally utilized and comply with relevant wiring rules, please follow the requirements below: 1) All UPS must be of the same rating and be connected to the same bypass source.
4.Operation 4.1 Operation Modes The UPS is a double-conversion on-line UPS that may operate in the following alternative modes : ◆ Normal mode The rectifier/charger derives power from the AC Mains and supplies DC power to the inverter while floating and boosting charge the battery simultaneously. Then, the inverter converts the DC power to AC and supplies to the load.
The internal fan of the UPS starts spinning, the UPS is performing self-diagnostics until buzzer beeps twice to show the UPS is normal. Then, the UPS goes to bypass supply, Utility LED and Bypass LED turn Green, the inverter is starting up now. When the inverter is checked “normal”, the UPS goes to working mode and the load is supplied by the inverter now.
4.2.4 Disconnecting with Utility CAUTION! This procedure should be followed to completely shut down the UPS and the LOAD. After all power switches, isolators and circuit breakers are opened, there will be no output. ◆After the inverter is off, turn the Utility and battery breakers to “OFF”, then the LCD display will extinguish completely and fan stops spinning in 60 seconds.
Page 17
Operational Status and mode When the UPS at single mode, it shows “NOA” or “ECO”or“CF”, but If the UPS at parallel mode, it shows “PAL” instead. 2) Press “DOWN” button, the UPS goes to next page as shown below. (2)Input voltage (3)Output voltage (4)Bat + voltage (Positive) (5)Bat –...
4.4 Parameters setting The setting function is controlled by 4buttons (ENTER/ON, ESC/OFF, UP,DOWN): ENTER ---goes into the setting page and value adjustment; UP & DOWN ---for choosing different pages. After the UPS turn ON, press buttons UP & DOWN for 3 seconds and then goes into the setting interface page.
Press ESC/OFF button to exit the output voltage setting (save the output voltage setting) and goes to mode setting or frequency setting. NOTE: When powered by inverter, it is necessary to turn off the inverter before setting voltage and frequency level. 4.4.3 Output frequency setting Frequency setting (Note: Inside the broken-line is the flashing part.)
Use button ENTER/ON to choose the different battery capacity. Battery capacity range is 1-200Ah. (Note: long-press of UP or DOWM can adjustment battery capacity quickly.) Press ESC/OFF button to exit the battery capacity setting (save the capacity setting) and goes to frequency setting or battery quantity setting.
Press ESC/OFF button to exit the bypass voltage upper limit setting (save the bypass voltage upper limit setting) and goes to battery quantity setting or bypass voltage lower limit setting. 4.4.7 Bypass Volt-Lo setting Bypass voltage lower limit setting (Note: Inside the broken-line is the flashing part.) When under the bypass voltage upper limit setting press DOWN or when under parallel ID setting press UP, it goes to the bypass lower limit setting.
4.4.9 Battery Test Setting Battery self-test setting This page is the introduction to the Battery self-test setting. The default Settings is “OFF” when the UPS has no need of the battery self-test function. When turn to “ON”, batteries can do the self-test automatically per 30 days. Three kinds of Battery Self-test Time can be chose as below.
4.4.10 Parallel ID setting Parallel ID setting (Note: Inside the broken-line is the flashing part.) When under the bypass voltage lower limit setting press DOWN or when under parallel quantity setting press UP, it goes to the parallel ID setting. The parallel ID flashes as in above picture.
4.4.12 Parallel redundancy quantity setting Parallel redundancy quantity setting (Note: Inside the broken-line is the flashing part.) When under the parallel quantity setting press DOWN, it goes to the parallel redundancy quantity setting. The parallel redundancy quantity flashes as in above picture. ...
Appendix 1 Specifications Capacity 6kVA/5.4kW 10kVA/9kW Type 6kVA;10kVA Input mode Single phase + Ground Power factor ≥0.99 208/220/230/240Vac(can be set) rating voltage rating frequency 50Hz/60Hz(auto sensing) Voltage range 120~276Vac Frequency range 45~55Hz/54~66Hz 220Vac max:10%,15%,20% or 25%,default :25% 230Vac max:10%,15% or 20%,default +20% Bypass voltage range 240Vac max:+10% or 15%,default +15% min:20%, 30% or 45%, default 45%...
Appendix 2 Communication port definition USB communication port Definition of Male port: Pin 1 VCC , Pin 2 D- pin 3 D+ , Pin 4 GND Application: use UPSilon2000 Power Management software Available functions of the USB ■ Monitor UPS power status ■...
Appendix 4 UPS message table This section lists the event and alarm messages that the UPS might display. The messages are listed in alphabetical order. This section is listed with each alarm message to help you troubleshoot problems . 4.1 Operational Status and Mode(s) Note:“X”...
Page 29
Item UPS Alarm Warning Buzz DC Bus below voltage Beep continuously Fault LED lit DC bus unbalance Beep continuously Fault LED lit Soft start failed Beep continuously Fault LED lit Rectifier Over Temperature Twice per second Fault LED lit Inverter Over temperature Twice per second Fault LED lit Reserve...
Need help?
Do you have a question about the M Series and is the answer not in the manual?
Questions and answers