  • Page 2 1KVAto3KVARack-Towerconversion  User’s Guide                                                                          ...
  • Page 3       Class B EMC Statements (High Voltage Models up to 3000 VA) FCC Part 15  NOTEThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice, pursuanttopart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotection againstharmfulinterferenceinaresidentialinstallation.Thisequipmentgenerates,usesandcan radiateradiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructions,may causeharmfulinterferencetoradiocommunications.However,thereisnoguaranteethat interferencewillnotoccurinaparticularinstallation.Ifthisequipmentdoescauseharmful interferencetoradioortelevisionreception,whichcanbedeterminedbyturningtheequipmentoff andon,theuserisencouragedtotrytocorrecttheinterferencebyoneormoreofthefollowing measures: ● Reorientorrelocatethereceivingantenna. ● Increasetheseparationbetweentheequipmentandthereceiver. ● Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiveris connected. ● Consultthedealeroranexperiencedradio/TVtechnicianforhelp.                ...
  • Page 4     Special Symbols  ThefollowingareexamplesofsymbolsusedontheUPSoraccessoriestoalertyoutoimportant information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol. CAUTION, need your attention This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This product contains sealed, lead‐acid batteries and must be disposed of properly.
  • Page 5: Table Of Contents

    Table of Contents 1  Introduction……………………………………………………………………………………………………5 2  SafetyWarnings………………………………………………………………………………………………6 3  Installation………………………………………………………………………………………………………7 4  Operation………………………………………………………………………………………………………19 5  Communication……………………………………………………………………………………………………………..35 6  UPSMaintenance…………………………………………………………………………………………..40 7  Specifications…………………………………………………………………………………………………44 Troubleshooting……………………………………………………………………………………………………………49  ...
  • Page 6: Introduction

        Introduction   ThisUPSprotectsyoursensitiveelectronicequipmentfrommostcommonpowerproblems,including powerfailures,powersags,powersurges,brownouts,linenoise,highvoltagespikes,frequency variations,switchingtransients,andharmonicdistortion.  Poweroutagesmightoccurunexpectedlyandpowerqualitycanbeerratic.Thesepowerproblems havepotentialtocorruptcriticaldata,destroyunsavedworksessions,anddamagehardware   — causinghoursoflostproductivityandexpensiverepairs. WiththeUPS,youcansafelyeliminatetheeffectsofpower disturbancesandguardtheintegrityofyourequipment.Providing outstandingperformanceandreliability,theUPS'suniquebenefitsinclude: True online double-conversion technology with high power density,utility frequency independence,andgeneratorcompatibility.Outputpowerfactorupto0.9. Threesegmentchargingmodetoincreasebatteryservicelife,optimizerechargetime. SelectableHighEfficiencymodeofoperation. ColdstartfunctiontostartuptheUPSwithoututility. Standard communication options: one RS-232 communication port, one USB communication port,andrelayoutputcontactsorSNMPcard. PowerSheddingfunctionmayturnoffuncriticalloadinbatterybackuptomakelongerbackup timeforcriticalload....
  • Page 7: SafetyWarnings

    Figure2 The Rackmount EBP front view        Safety Warnings   IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installationandmaintenanceoftheUPSandbatteries.Pleasereadallinstructions beforeoperatingtheequipmentandsavethismanualforfuturereference.   DANGER  TheUPScontainsLETHAL VOLTAGES.Allrepairsandserviceshouldbeperformed byAUTHORIZED SERVICE PERSONNEL ONLY. ThereareNO USER SERVICEABLE  PARTSinsidetheUPS.     WARNING  TheUPScontainsitsownenergysource(batteries).TheUPSoutputmaycarry livevoltageevenwhentheUPSisnotconnectedtoanACsupply. Toreducetheriskoffireorelectricshock,installtheUPSinatemperatureand   humidity controlled, indoor environment, free of conductive contaminants. Ambienttemperaturemustnotexceed40°C(104°F).Donotoperatenearwater orexcessivehumidity(90%maximum).  Toreducetheriskoffire,connectonlytoacircuitprovidedwithbranchcircuit...
  • Page 8: Installation

    precautions.Keepunauthorizedpersonnelawayfrombatteries. Proper disposal of batteries is required. Refer to your local codes for disposal requirements. Never dispose of batteries in a fire. Batteries may explode when exposed to flame.     Installation   Thissectionexplains: Equipmentinspection Unpackingthecabinet Checkingtheaccessorykit Cabinetinstallation Wiringinstallation Initialstartup Inspecting the Equipment Ifanyequipmentreceivedhasbeendamagedduringshipment,keeptheshipping cartonsandpackingmaterialsforthecarrierorplaceofpurchaseandfileaclaimfor...
  • Page 9: Rackmount Installation

    USBcable Powercord(Inputandoutput)  RS232cable IfyouorderedanoptionalExtendedBatteryModule(EBP),verifythatthefollowingadditional itemisincludedwiththeEBP: ●  EBPuser'sguide NOTEDiscardtheEBPuser'sguideifyouareinstallingtheEBPwithanewUPSatthesametime.Use theUPSuser'sguidetoinstallboththeUPSandtheEBP. Rackmount Installation       The Rackmount cabinet comes with all of the hardware required for installation in a standardEIAorJISseismicRackmountconfigurationwithsquareandroundmountingholes. The rail assemblies adjust to mount in 19” racks with a distance from front to rear around 70~76cm(27to30inches)deep. Checking the Rail Kit Accessories(Options) ...
  • Page 10  Toinstalltherailkit: 1.  AssembletheleftandrightrailstotherearrailsasshowninFigure3.Donottightenthescrews. Adjusteachrailsizeforthedepthofyourrack.                                     Figure3 Securing the Rails 2. SelectthepropersizeintherackforpositioningtheUPS(seeFigure4).Therailoccupiesfour positionsonthefrontandrearoftherack. 3. TightenfourM5UmbrellaNutsinthesideofrailassembly(seeFigure3). 4. FixonerailassemblytothefrontoftherackwithoneM5×12pan-headscrewandoneM5cage nut.UsingtwoM5cagenutsandtwoM5×12pan-headscrews,tofixtherailassemblytotherear oftherack.            ...
  • Page 11 9. AlignthemountingbracketswiththescrewholesoneachsideoftheUPSandfixwiththe suppliedM4×8flat-headscrews(seeFigure5)                        Figure5 Installing the Mounting Brackets  10.  Ifinstallingoptionalcabinets,repeatStep8and9foreachcabinet. 11.  SlidetheUPSandanyotheroptionalcabinetsintotherack. 12.  SecurethefrontoftheUPStotherackusingoneM5×12pan-headscrewsandoneM5cagenuts       oneachside(seeFigure6).Installthebottomscrewoneachsidethroughthebottomholeof  mountingbracketandthebottomholeoftherail. Repeatforanyoptionalcabinets. Figure6 Securing the Front of the Cabinet  Continuetothefollowingsection,“RackmountWiringInstallation. Rackmount Wiring Installation hissectionexplains:             T InstallingtheUPS,includingconnectingtheUPSinternalbatteries ConnectinganyOptionalEBP(S)...
  • Page 12 Installing the UPS  Donotmakeunauthorizedchangestotheups;otherwise,damagemayoccur NOTE toyourequipmentandvoidyourwarranty. Do not connect the ups power cord to utility until after installation is NOTE  completed. ToinstalltheUPS: 1.RemovethefrontcoverofeachUPS    HoldthecoverpartwithoutLCDontherightsideandextractit(seeFig.7)                  Figure7 Extract UPS front cover C A U T I                 ...
  • Page 13 Figure8 Connecting the UPS Internal Batteries  3.IfyouareinstallingEBPS,seethefollowingsection, “ConnectingtheEBP(s),” beforecontinuing      withtheUPSinstallation. 4. ReplacetheUPSfrontcover. Toreplacethecover,verifytheEBPcableisroutedthroughtheknockoutonthebottomofthecover ifEBPSareinstalled.  Putthefrontcoverhooksofsidewithdisplaytothecoverport,putanothersidetotheothertwo ports,thenpressituntilthecoverandthechassisarecombinedtightly.  Figure9    ...
  • Page 14 5. Ifyouareinstallingpowermanagementsoftware,connectyourcomputertooneofthe communicationportsoroptionalconnectivitycard.Forthecommunicationports,useanappropriate cable. 6. Ifyourrackhasconductorsforgroundingorbondingofungroundedmetalparts,connectthe groundcable(notsupplied)tothegroundbondingscrew.See“RearCovers”forthelocationofthe groundbondingscrewforeachmodel. 7. Ifanemergencypower-off(disconnect)switchisrequiredbylocalcodes,see“RemoteEmergency Power-off” (REPO)toinstalltheREPOswitchbeforepoweringontheUPS. 8. Continueto “UPSInitialStartup”. Connecting the EBP(s)  ToinstalltheoptionalEBP(s)foraUPS: 1.RemovethefrontcoverofeachEBPandUPS(seeFigure10).  Itisthesamewiththeinstallationofthefrontcover.(Refer”ToinstalltheUPS“)   Figure10 Removing the EBP Front Cover 2. OnthebottomoftheUPSfrontcover,removetheEBPcableknockout(seeFigure11). Figure11 Removing the UPS Cable Knockout   3. Forthebottom(oronly)EBP,removetheEBPcableknockoutonthetopoftheEBPfrontcover.See Figure12forthelocationofthetopEBPcableknockout. 4. IfyouareinstallingmorethanoneEBP,foreachadditionalEBPremovetheEBPcableknockouton thetopand bottomoftheEBPfrontcover.SeeFigure12forthelocationoftheEBPcableknockouts.  ...
  • Page 15                                        CAUTION  AsmallamountofarcingmayoccurwhenconnectinganEBPtotheUPS.Thisisnormalandwillnot harmpersonnel.InserttheEBPcableintotheUPSbatteryconnectorquicklyandfirmly. 5. PlugtheEBPcable(s)intothebatteryconnector(s)asshowninFigure12.UptofourEBPSmaybe...
  • Page 16   Rackmount converted to Tower Installation RackmountconvertedtoTowerplasticbaseinstallation  ①  two plastic base brackets  ②  flatten it after intercrossing                    intercross as following Figure    Figure 13 plastic base installation    ③IfanEBPisneededtobeplacedinthemiddle,theassemblyofplasticbaseissimilar, Thedifferenceisthattwo1Uplasticbaseextendedboardsareaddedinthemiddle.(asthefollowing shows)   (A)                                                                   ...
  • Page 17   (E)                                                                (F)                             ...
  • Page 18     Figure15 The installation for UPS and battery box  1.Installthebase,thenplacetheRTUPSonthebaseonebyoneasFig.15shows. 2.ThecoverinstallationandcableconnectionoftheUPSandEBPSarethesameasRT.(Toinstallthe optionalEBP(s)foraUPS) UPS Initial Startup TostartuptheUPS:    NOTE  Verify that the total equipment ratings do not exceed the UPS capacity to preventanoverloadalarm. 1.IfoptionalEBPsareinstalled,verifythattheEBPsareconnectedtotheUPS.  2.  Plug the equipment to be protected into the UPS, but do not turn on the protectedequipment. 3.  Makeanynecessaryprovisionsforcordretentionandstrainrelief. 4.  PlugthedetachableUPSpowercordintotheinputconnectorontheUPSrear...
  • Page 19  7.  PressthecombinationstartupbuttonsontheUPSfrontcoverforatleasthalfa second.TheUPSwillstartupandtheLEDwillturnonandoffsequentially.  8.  Check the UPS front cover display for active alarms or notices. Resolve any active alarms before continuing. See Troubleshooting” on page 49. If the indicator is on, do not proceed until all alarms are clear.Check the UPS statusfromthefrontcovertoviewtheactivealarms.Correctthealarmsand restartifnecessary. 10.  Verify that the...
  • Page 20: Operation

    Operation    This chapter contains information on how to use the UPS, including front cover operation, operating modes, UPS startup and shutdown, transferring the UPS between modes, and configuringbypasssettings,loadsegments,andbatterysettings. Control Cover Functions TheUPShasathree-buttonsegmentalLCDwithbacklight.Itprovidesusefulinformationabout theUPSitself,loadstatus,measurements,andsettings(seeFigure16).          Figure16. Control Cover  Table 1. Indicator Descriptions ...
  • Page 21   Table 2 . Button function    Button Function description Start up combination ( ) RT  Press and hold this key for more than half a secondtoturnontheUPSortoturnofftheUPS.   Shutdown/Rotating RT  Pressandholdthiskeyformorethan2seconds combination tocircumrotatetheLCD. ( ) Pressandholdthekeyformorethan1secondinLine mode or economic(ECO) mode: UPS runs self-test Battery test/Mute function....
  • Page 22 voltage everyfour seconds Battery Voltage Onceper ● ★ ★ abnormal second warning Bypassmode MainAC Once Normal Eliminateafter ● ★ everytwo voltagein startingtheUPS minutes bypassmode MainAChigh Once voltage ★ everyfour warningin seconds bypassmode MainAClow Once voltage ★ everyfour warningin seconds bypassmode Batterydisconnectwarning Once Affirmifthe...
  • Page 23 ●_indicatorlightsforalongtime ★_indicatorflashes ▲_thestatusofindicatordependsonotherconditions Display Functions  Asthedefaultorafter5minutesofinactivity,theLCDdisplaysthe outputparameters. ThebacklitLCDautomaticallydimsafter5minutesofinactivity.Press anybuttontorestorethescreen. LCDdisplaycomprisesnumericalvaluesection,capacitygraphicssection,fan-statusgraphicssection andcharger-statusgraphicssection,refertoTable4fordetail. Table4.LCDdisplaysection Section Description Graphic Display the corresponding numerical value of inquiring items(output, load, Numerical temperature, input, battery), for value  example,asthegraphicsshowsabove, section theoutputvoltageis230v,theoutput frequencyis50Hz. Displaythecapacityofthebatteryand load. Every pane represents 20 % capacity. As graphics shown above, Capacity  the capacity of the battery is 80 %...
  • Page 24 Displaythestatusofthecharger.  When charger works normally, the corresponding icon will vary Charger-status dynamicallyandorderly. graphics when charger works abnormally, the section iconwillkeepflashing When UPS is in battery mode, the number the icons the charger-state section will vary accordingtothechangeablecapacity ofthebattery(pane).     Parameters inquiring ...
  • Page 25: User Settings

    Display the temperature of the inverter in the UPS. As  the following graphics shown: the Temperature temperatureoftheinverteris37℃. Display the voltage and frequency of the input. As the following Input graphicsshown:theinputvoltageis 210v,inputfrequencyis49.8Hz. Displaythevoltageandcapacityof the battery . As the following Battery graphicsshown:thebatteryvoltage is 38v, the capacity of battery is 100 %...
  • Page 26 Setting function(serial Settingprocedure LCD display number) ① Enter the setting interface.   Press and hold the function   setting key for more than 2   seconds, then come to setting     interface, the letters “ECO” willflash.   ② Enter the ECO setting  ...
  • Page 27 2 seconds, then come to settinginterface,shortpress   the scroll key for more   thanhalfasecond(lessthan 2 seconds) to select BPS setting, the letters “bPS” Bypass willflash. function ② Enter the BPS setting setting(2) interface. Press and hold the functionsettingkey formore than half a second(less than 2 seconds)atthistime,theletters  ...
  • Page 28 morethanhalfasecond(less than 2 seconds), select the function setting, choose output voltage setting interface,atthemoment,the letters“OPU”willflash. ② Enter the output voltage selectinginterface.Pressand hold the function setting for more than half a second(lessthan2seconds), then come setting interface of output voltage OPU,atthistime,theletters “OPU”willlightforalong time. The numerical value below the OPU will flash. Press and hold the scroll for more than half a...
  • Page 29 functionsettingkey formore Battery string than half a second(less than 2 number and seconds), then come to setting type interface of battery, the letters setting(4) “bAt” will stop flashing. The numerical value below the “bAt” will flash. Press and hold the scroll key for more than half a second (less than 2 seconds), select the numerical...
  • Page 30 the function setting key for more than half a second (less than 2 seconds). Now, the load shielding battery voltage settingisconfirmed. ④  Exit from the setting interface. Press and hold functionsettingkey formore than half a second (less than 2 seconds), exit from the setting interface and return to main interface....
  • Page 31 ① Enter the setting interface. Frequency Press and hold the function Converter setting key for more than mode setting 2 seconds, then come to (7) setting interface, Press and hold the scroll key for morethanhalfasecond(less than 2 seconds), select the function setting, choose output frequency setting interface,...
  • Page 32 ①  Enter the setting interface. Parameter Press and hold the function reset setting key for more than 2 factory seconds, then come to setting Setting(8) interface, Press and hold the scrollkey formorethanhalfa second(less than 2 seconds), select the function setting, choose parameter reset setting interface, the letters “RESET” willflash.
  • Page 33 instable,UPSwillturntobatterymode atonce.Ifthemainsrecovers,theUPS willtransfertolinemode. If battery low alarm activates, the Battery indicator of  flashes. If battery Mode voltagereacheslowlimit,UPSwillturn off to protect the battery. UPS will auto-restartwhenthemainsrecover. NOTE:Thebackuptimeofbattery mode is subject to the load and EBP numbers. Battery remaining time displayed on the LCD may not be accurate. Bypass yellow LED is on, the buzzer beeps once every 2 minutes . The...
  • Page 34 WhenUPSispluggedintolineandnot    Standby turnon,theUPSwillworkinstandby Mode mode to charge the battery. No indicatordisplaysonthismode.   UPS Turn on and Turn off Start up operation  Turn on the UPS in line mode  1.   Oncemainspowerispluggedin,theUPSwillchargethebattery,atthemoment,theLCDshows thattheoutputvoltageis0,whichmeanstheUPShasnooutput.Ifitisexpectedtohavethe outputofbypass,youcansetthebps“ON”byLCDsettingmenu. 2.  PressandholdtheONkeyformorethanhalfasecondtostarttheUPS,thenitwillstartthe inverter. 3. Oncestarted,theUPSwillperformaself-testfunction,LEDwilllightandgooutcircularlyand orderly.Whentheself-testfinishes,itwillcometolinemode,thecorrespondingLEDlights,the UPSisworkinginlinemode. Turn on the UPS by DC without mains power  1. Whenmainspowerisdisconnected,pressandholdtheONkeyformorethanhalfasecondto startUPS. 2. TheoperationoftheUPSintheprocessofstartisalmostthesameasthatwhenmainspoweris in.Afterfinishingtheself-test,thecorrespondingLEDlightsandtheUPSisworkinginbattery mode....
  • Page 35 Configuring Battery Settings  SettheUPSforthenumberofEBPsinstalled.  Toensuremaximumbatteryruntime,configuretheUPSforthecorrect numberofEBPs,refertoTable8fortheappropriatesettingofbatterynumbersandtype. Usetheupanddownscrollkeystoselectthenumberofbatterystringsaccordingtoyour UPSconfiguration: Table 8 Battery number Configuration        All UPS and EBP Cabinets        Number of Battery Strings  UPSonly(internalbatteries)        1(default)       UPS+1EBP             3       UPS+2EBPs             5       UPS+3EBPs...
  • Page 36: Communication

    5. Communication  Thissectiondescribesthe: ● Communicationports(RS-232andUSB) ● Connectivitycards ● EmergencyPower-off(EPO) ● LoadSegments ● UPSilon2000PowerManagementSoftware See “RearCovers” onpage49forrearcoverdiagramsforeachmodel.    Figure 17. Figure18 CommunicationOptionsandControlTerminals Installing Communication Options and Control Terminals Toinstallthecommunicationoptionsandcontrolterminals: 1.   Installtheappropriateconnectivitycardand/ornecessarycable(s)andconnect thecablestotheappropriatelocation. 2.   Routeandtiethecable(s)outoftheway. 3.   Continueto “Operation” onpage17/18tostartuptheUPS.    Communication Options The UPS has serial communication capabilities through the USB and RS-232 communicationportsorthroughaconnectivitycardintheavailablecommunication...
  • Page 37 : NOTE The communication speed of the RS232 port is fixed at 2400 bps. RS-232 and USB Communication Ports To establish communication between the UPS and a computer, connect your computer to one of the UPS communication ports using an appropriate communicationcable(notsupplied).SeeFigure17,18forthecommunicationport locations. When the communication cable isinstalled, power management software can...
  • Page 38   Connectivity Cards    ConnectivitycardsallowtheUPStocommunicateinavarietyof networking environments and with different types of devices. The UPS has one availablecommunicationbayforthefollowingconnectivitycards: ● Web/SNMP  Card  - has SNMP and HTTP capabilities as well as monitoring through a Web browser interface; connects to a twisted-pair Ethernet (10/100BaseT) network. In addition, a Environmental Monitoring Probe can be attachedtoobtainhumidity,temperature,smokealarm,andsecurityinformation.  ● Relay ...
  • Page 39 emergencypower-offfunctionisactivated. NOTE ForEurope,theemergencyswitchrequirementsaredetailedinHarmonized documentHD-384-48S1, “ElectricalInstallationoftheBuildings,Part4:Protection forSafetyChapter46:IsolationandSwitching.” EPO Connections Wire Function          Terminal Wire Size Rating              Suggested Wire Size EPO   L1                  4–0.32mm2(12–22AWG)        0.82mm2(18AWG)        L2...
  • Page 40   Figure 22 Load Segments  UPSilon2000PowerManagementSoftware  EachUPSshipswithUPSilon2000PowerManagementSoftware.Tobegininstalling UPSilon2000software,seetheinstructionsaccompanyingtheSoftwareSuiteCD.  NOTEInstallUPSilon2000powermanagementsoftwarewiththe  serialnumber attchedonthecoveroftheCD.Whenrunningthemonitorsoftware,choose appropriatecommunicationport.IfusingRS232,chooseCOM1/2andMegatec protocol.IfusingUSB,choosemegatecUSB.  UPSilon2000softwareprovidesup-to-dategraphicsofUPSpower  andsystem dataandpowerflow.Italsogivesyouacompleterecordofcriticalpowerevents, anditnotifiesyouofimportantUPSorpowerinformation.Ifthereisapoweroutage andtheUPSbatterypowerbecomeslow,UPSilon2000softwarecanautomatically shutdownyourcomputersystemtoprotectyourdatabeforetheUPSshutdown occurs.  ...
  • Page 41: UpsMaintenance

    6    UPS Maintenance                    Thissectionexplainshowto:  CarefortheUPSandbatteries ReplaceExtendedBatteryPacks(EBPs) Testnewbatteries RecycleusedbatteriesorUPS UPS and Battery Care Forthebestpreventivemaintenance,keeptheareaaroundtheUPScleananddust‐ free.Iftheatmosphereisverydusty,cleantheoutsideofthesystemwithavacuum cleaner.Forfullbatterylife,keeptheUPSatanambienttemperatureof25°C(77°F).  NOTE  The batteries in the UPS are rated for a 3–5 year service life. The length of servicelifevaries,dependingonthefrequencyofusageandambienttemperature. Batteries used beyond expected service life will often have severely reduced runtimes. Replace batteries at least every 5 years to keep units running at peak...
  • Page 42 Replacing RT UPS and EBPS    1.Ifthebatteryfault,thefollowingstepsareprovidedformodularunittoreplacethenewbattery pack 2.Removethefrontcoverofthebatterybox. 3.RemovetheconnectioncablesbetweenbatteryboxandUPS.Releasethescrewofthebaffleofthe batterypackastheFig.23shows,thenremovethebafflefromtheleftorright.   Fig.23    The Installation for baffle of battery pack              4.Graspthehandleinfrontofthebatterypack,takeoutofitandholdit,thenremovethebattery packasfig.24shown.  ...
  • Page 43   Fig.24 Remove the battery park  5.Holdthemiddleofthenewbatterypack,insertit.Onceinstallthenewbatterypack,makesureitis completelyinsertedintothechassisasfig25shown.                                    Fig.25 Installation for battery pack  Testing New Batteries  Totestnewbatteries: 1.PlugtheUPSintoapoweroutletfor48hourstochargethe batteries. 2.StartuptheUPSbypressingthestartupcombinationbutton. 3.Pressthebatterytestcombinationbuttontoactivatethebatterytest. TheUPSstartsabatterytestifthebatteriesarefullycharged,the UPSisinNormalmodewithnoactivealarms,andthebypass voltageisacceptable. Duringthebatterytest,theUPStransferstoBatterymodeand  ...
  • Page 44: Recycling The Used Battery Or Ups

    dischargesthebatteriesfor10seconds.TheLEDindicatorsofthefrontcoverstopcyclingwhenthe testiscompleted. Recycling the Used Battery or UPS Contact your local recycling or hazardous waste center for information on proper disposaloftheusedbatteryorUPS. WARNING   Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper disposal ofbatteries isrequired. Refer toyourlocalcodes for disposal  ...
  • Page 45: Specifications

    Communication Bay  availableindependentcommunicationbayforconnectivitycards Compatible  SNMPcard/ContactRelayCard Connectivity Cards RS232(DB-9):2400bps Communication  Ports USB Table 11   Extended Battery Model  EBP Model   Configuration Battery Voltage   For Power Ratings   1K–EBP 24Vdc 1000VA 1.5K-EBP 36Vdc  1500VA  2K-EBP  48Vdc  2000VA  3K-EBP 72Vdc 3000VA Table 12. UPS Model List (All Models)  Model Power Level Rear Cover Diagram...
  • Page 46 440*572*86.5mm  26.3kg   RT 440*696*86.5mm  33.0kg   RT Model (RT EBP) Dimensions (W*D*H) Weight 440*430*86.5mm  19.0kg   RT 440*430*86.5mm  24.0kg  1.5K-  RT 440*572*86.5mm  33.6kg   RT 440*690*86.5mm  46.0kg   RT Table 14. Electrical Input (All Models)  Nominal Frequency 50/60Hzauto-sensing 45–55Hz(50Hz)/55-65Hz(60Hz)beforetransferto Frequency Range battery +5%,+10%,+15%,+25%(+25%by Bypass Voltage Range default),-20%,-30%,-45%(-45%bydefault)...
  • Page 47   Table 17. Electrical Output (All Models)  High Voltage Models 200/208/220/230/240V (voltageconfigurableor auto-sensing) Nominal Outputs 1000/1500/2000/3000VA 0.9/1.35/1.8/2.7kW Frequency 50or60Hz,autosensing 108%±5%–150%±5%:LoadtransferstoFaultmodeafter 30seconds.  Output Overload  150%±5%–200%±5%:LoadtransferstoFaultmodeafter (Normal Mode) 300ms.  >200%±5%:LoadtransferstoFaultmodeafter20ms.  100%±5%–130%±5%:LoadtransferstoFaultmodeafter 20minutes. 130%±5%–150%±5%:LoadtransferstoFaultmodeafter Output Overload  2minutes. (Bypass Mode) 150%±5%–200%±5%:LoadtransferstoFaultmodeafter 15seconds. >200%±5%:LoadtransferstoFaultmodeafter140ms. 108%±5%–150%±5%:LoadtransferstoFaultmodeafter 30seconds. Output Overload  150%±5%–200%±5%:LoadtransferstoFaultmodeafter (Battery Mode) 300ms. >200%±5%:LoadtransferstoFaultmodeafter20ms. Voltage Waveform Sinewave Harmonic  <3%THDonlinearload;<5%THDonnon-linearload Distortion Onlinemode:0ms(nobreak)...
  • Page 48 Table 18. Electrical Output Connections (All Models)  Model Output Connections Output Cables (IECC13-10A)*6 IEC320C14-10A  RT 1.5K- (IECC13-10A)*6 IEC320C14-10A  RT (IECC13-10A)*6 IEC320C14-10A  RT IEC320C14-10A (IECC13-10A)*6       RT (IECC19-16A)*1 IEC320C20-10A Table 19. Environmental and Safety (All Models)  208/230/240 Vac Models EN61000-2-2 EN61000-4-2,Level4 Surge  EN61000-4-3,Level3 Suppression EN61000-4-4,Level4(alsoonsignalports) EN6100-4-5,Level4CriteriaA CEperIEC/EN62040-2, EMC  ClassB Certifications ClassB EMC  IEC62040-2:ed2:2005/EN62040-2:2006 (Emissions) Safety ...
  • Page 49 1.5K NOTEBatterytimesareapproximateandvarydependingontheload configurationandbatterycharge. Table 21. Battery                          Internal Batteries EBPs 1000VA:24Vdc(2,  12V,9Ah)  1K-EBP:24Vdc(2x2,12V,9Ah)  1500VA:36Vdc(3,  12V,9Ah) Battery  1.5K-EBP:36Vdc(2x3,12V,9Ah)  Configuration 2K-EBP:48Vdc(2x4,12V,9Ah)  2000VA:48Vdc (4,12V,9Ah)    3K-EBP:72Vdc(2x6,12V,9Ah)...
  • Page 50: Troubleshooting

    Rear Covers  Figure 26.      Figure 27. 8 Troubleshooting  The following messages are the information that users would find on UPS when it meets some problems.Userscanjudgeifthefaultiscausedbyexternalfactorsandknowhowtodealwithitby makingfulluseoftheinformation. Faultindicatoron,indicatesthattheUPShasdetectedsomefaults.Buzzerbeeps,indicatesthatUPS needtobepaidattentionto,ifbeepsforalongtime,itmeansthatthereissomethingwrongwiththe machine. If you need help, contact our service department, the following messages should be providedforanalysis: ◆UPSMODELNO.andSERIALNO. ◆Dateoffaulthappened...
  • Page 51 Whenreplacebattery,contact Batteryaged franchisertogetbatteryand relativeassembly Didn’tpressthe Pressthetwokeysatthesame combinationkeysof time “on” UPSdoesn’t UPShasnobattery ConnectUPSbatterywell,if startupafter connectedorbattery batteryvoltagelow,pleaseturn pressingtheON voltagelowandtoo offUPSandremovesomeloads, key manyloadsconnected thenstartUPS Faultoccursinside Contactsupplierforservicing UPS Theiconof chargerstatuson Chargerdoesn’twork LCDdisplay normallyorbattery Contactsupplierforservicing flashesandbuzzer aged beepsonceper second Thefollowingtabledescribestypicalfaultyconditions. Table 23. Fault code for RT type    OperatingModebeforefault FaultKind Faulttype BypMode LineMode BatMode...