LG LB-R0551QC Owner's Manual page 30

Ceiling duct-type air conditioner

Advertisement

Installer Setting - Setting Address of Central Control
This procedure is used to set up the address of Indoor units.
Please refer to central controller manual for connecting Indoor units with the control controller
1
If pressing
button long for 3
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
2
If entering into address setup mode by using
button, it indicates as picture below.
3
Set Group No. by pressing
button.(0~F)
4
Move to Indoor No. setting option
by pressing
5
Set Indoor No. by pressing
button.
6
Press
button to save.
7
Pressing
button will exit settings mode.
After setup, it automatically gets out of
setup mode if there is no button input for
25 seconds.
When exiting without pressing set button,
the indoor unit address will not set.
30
Indoor No.
Group No
Function Code
button.