Page 1
The difference is related to the cable clamp which fits to the cable gauge: Clamp-1 (16 > 50mm Clamp-2 (70 > 120mm NB : the cable clamp model number and the polarities are engraved in the plastic part. WIIQ3 user Manual rev 05/2018...
Page 2
Cable clamp O-ring Caution: there is an O-ring seal between the Wi-iQ3 main unit and the protective cover. Make sure the O-ring is still properly located in the main unit when assembling the current sensor. WIIQ3 user Manual rev 05/2018...
Page 3
5. Assemble the current sensor on the main unit (torque 1.5Nm ±0.1). Make sure to use the appropriate screws (delivered with the current sensor). Current sensor 14mm screws Towards the plug Towards the battery Caution: using inappropriate screws (type and length) may damage the product and impact its reliability. WIIQ3 user Manual rev 05/2018...
Page 4
Caution: using inappropriate screws (type and length) may damage the product and impact its reliability. 8. Fasten the DC cables with cable ties at each side of the Wi-iQ3 to avoid stressing the connections during handling. WIIQ3 user Manual rev 05/2018...
Page 5
BLE T° 12V (EMEA/ASIA) The sensors are communicating with Wi-iQ3 unit via Bluetooth Low Energy (BLE) process (they are also called BLE sensors). The pairing process with a Wi-iQ3 unit is described in the Pairing section. WIIQ3 user Manual rev 05/2018...
Page 6
For connecting each wire on the battery, use only the genuine parts supplied with the BLE sensor: • black voltage tap for ANY wire • heat-shrinkable crimping splice Wire connection assembly details NB: a BLE sensor includes its own protective fuse then the connection materials shall not include any additional fuse. WIIQ3 user Manual rev 05/2018...
Page 7
There are two LEDs on the top of each sensor for status indication. Color Confidence blinking Slow Alternate Unlit (every 32s) blinking blinking High temperature Misfunction Identification Normal Blue Low water level Normal status sequence status (unit in function) WIIQ3 user Manual rev 05/2018...
Page 8
2. Assemble the CAN option on the main unit (torque 1.5Nm ±0.1). Make sure to use the appropriate screws (delivered with the CAN option). CAN option 14mm screws Caution: using inappropriate screws (type and length) may damage the product and impact its reliability. WIIQ3 user Manual rev 05/2018...
Page 9
(2) If the Smartphone is not connected to Internet during scan and data download, the transfer to the remote server will be done as soon as the Internet connection is restored. The main screens of the App with the main parameters are shown in the next pages. WIIQ3 user Manual rev 05/2018...
Page 10
(6) The ‘Identification’ button allows to visually identify the selected device through the identification sequence of its LEDs. (7) As long as the Wi-iQ3 is connected to the App, there is no communication with the BLE sensor (i.e. temperature data is not refreshed). WIIQ3 user Manual rev 05/2018...
Page 11
The process to associate (i.e. to pair) a BLE sensor to a Wi-iQ3 unit is described below: 1. With the E connect Mobile App (using Bluetooth) • After installing the Wi-iQ3 and BLE units on the battery WIIQ3 user Manual rev 05/2018...
Page 12
• Enter in the BLE section • Tick the Active box • Enter the BLE Sensor Address (MAC) • Tick the appropriate boxes and set cells balance number depending on the BLE sensor model • Click on Write WIIQ3 user Manual rev 05/2018...
Page 13
CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION. IN ACCORDANCE WITH FCC REQUIREMENTS, CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY ENERSYS COULD VOID THE USER'S AUTHORITY TO OPERATE THIS PRODUCT.
Need help?
Do you have a question about the WIIQ3 and is the answer not in the manual?
Questions and answers