Removal of low pressure switch from combination boilers
Hide thumbs Also See for VTXCOMBI26:

Advertisement

Grant Vortex
Removal of low pressure switch from the Grant
vortex pro range of Combination boilers
Contents
1

IntRoDUCtIon

2
Removal of CURRent
swItCh
3
1
IntRoDUCtIon
1.1
GeneRal
! waRnInG !
Do not remove the low pressure switch if there is plastic
pipework fitted on the system.
This cap is intended for use on the following Grant UK boilers:
Internal Combi models (yellow flame):
VTXCOMBI21
VTXCOMBI26
VTXCOMBI36
VTXXSCOMBI26
External Combi modules (yellow flame):
VTXOMCOMBI21
VTXOMCOMBI26
VTXOMCOMBI36
Internal Combi models (blue flame):
VTXBFCOMBI21
VTXBFCOMBI26
VTXBFCOMBI36
External Combi modules (blue flame):
VTXBFOMCOM21
VTXBFOMCOM26
VTXBFOMCOM36
! note !
All work is to be carried out by a trained and competent
person.
1.2

KIt Contents

1 x ¼ʺ cap
pRoDUCt CoDes CoveReD
These instructions cover the following product codes:
MPCBSCAP
2
1
The procedure for removing the current low pressure switch is as
1
follows:
Firstly, set the boiler on/off switch to OFF and ensure the boiler is
isolated from the electrical supply at the fused spur/isolator.
2
1.
2.
3.
4.
5.
6.
7.
8.
1.
2.
3.
4.
5.
6.
7.
page 1
Removal of CURRent
swItCh
Remove the front and top front casing panels.
Remove the two screws securing the terminal block cover
and lift off the cover.
Loosen (do not remove) the four screws securing the control
panel to the side panels, hinge the panel forward and allow it
to drop down to gain access to the top of the panel.
Remove the screws securing the cable clamp and the p-clip.
Disconnect the low pressure switch cable connections from
terminals 15 and 16 (blue and brown wires).
To prevent excessive water entering the boiler, remove the
initial system pressure by ensuring that the filling loop has
been isolated. Then open up the drain valve at the front of
the boiler and contain any fluid in a suitable receptacle.
! CaUtIon !
allow the boiler to cool before releasing water pressure
from the heating system.
Isolate the low pressure switch pipework by closing the pump
valve on the flow and the isolation valves on the return.
Disconnect the low pressure switch by undoing the threaded
connection and remove from the boiler.
Remove the boiler door, top casing panel and insulation from
the boiler.
Remove the two screws at the top of the control panel (in
cross member) and allow the panel to hinge forward.
Remove the two screws securing the cable clamp.
Disconnect the low pressure switch cable connections from
terminals 15 and 16 (blue and brown wires).
To prevent excessive water entering the boiler, remove the
initial system pressure by ensuring that the filling loop has
been isolated. Then open up the drain valve at the front of
the boiler and contain any fluid in a suitable receptacle.
! CaUtIon !
allow the boiler to cool before releasing water pressure
from the heating system.
Isolate the low pressure switch pipework by closing the pump
valve on the flow and the isolation valves on the return.
Disconnect the low pressure switch by undoing the threaded
connection and remove from the boiler.
october 2017
DoC 0119
Rev 1.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VTXCOMBI26 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Grant VTXCOMBI26

  • Page 1 Do not remove the low pressure switch if there is plastic initial system pressure by ensuring that the filling loop has pipework fitted on the system. been isolated. Then open up the drain valve at the front of This cap is intended for use on the following Grant UK boilers: the boiler and contain any fluid in a suitable receptacle. • Internal Combi models (yellow flame): ! CaUtIon ! •...
  • Page 2 To tilt the top panel, loosen the four top panel casing screws, one at each corner and push down on the side furthest from the wall. Tighten the screws. GRant enGIneeRInG (UK) lImIteD Hopton House, Hopton Industrial Estate, Devizes, Wiltshire, SN10 2EU Tel: +44 (0)1380 736920 Fax: +44 (0)1380 736991 Email: info@grantuk.com www.grantuk.com...

This manual is also suitable for:

Vortex pro seriesVtxcombi21Vortex combi seriesVtxcombi36Vtxxscombi26Vtxomcombi21 ... Show all

Table of Contents