6. DIP SWITCHES
DIP ON
1
Tamper disabled
2
Not used
OUT active to GND
3
4
CS input active at +12V
5
SI input active at +12V
6
ALL input active at +12V
7
Power ON
Smoke enabled
8
7. DIAGNOSTIC LEDs
BLUE
Lampeggia durante il periodo di preallarme.
GREEN
A brief flash indicates the triggering of the
smoke capsule. Useful during installation.
RED
Reports the smoke capsule is empty.
8. OUTPUTS
NUBI can be driven only with CS input (immediate discharge), or using the SI and ALL inputs in conjunction by the
integrated infrared sensor. The operating logic is shown in the following diagram:
Installation manual NUBI F1
OFF
Tamper active
Not used
OUT active open
CS input active at GND
SI input active at GND
ALL input active at GND
Power OFF
Smoke disabled
The 24H output is a clean contact
that is always closed when the box
is closed or the DIP1 is ON..
The OC output switch to GND for
90
seconds
after
the
capsule run. Useful to drive the
internal siren or an external alarm
device.
The OUT output become active
when the smoke capsule is empty.
It can be active open or to GND,
according to DIP 3.
Press the Walk Test button to activate the diagnostic
function for 10 minutes to turn on the blue LED every time
the passive infrared detects movement. This allows to
position the device to obtain the maximum coverage of the
built-in infrared. When the Walk Test mode is active, the
next press of the button will stop it.
IMPORTANT: Keep OFF the DIP 7 and 8 during wiring.
Set DIP 7 to ON to power the board and carry out the
tests, only at the end of installation job put ON the DIP 8
to enable the smoke capsule.
The simulation tests of the smoke delivery keeping the
DIP 8 in the OFF position, can only be performed within
4 hours from the power supply of the board, after
which the validation board will be irreparably consumed.
It is therefore recommended to switch OFF and ON
again the device with DIP 7 as the first thing to do in
case of maintenance to a device installed for a long
time.
smoke
Before the final commissioning, it is advisable to carry out
both the Walk Test and some real simulations, with the
DIP8 in the OFF position, where the green LED will emit a
short flash that simulates the ignition of the fumigation
capsule.
At the end of the installation, remove
the adhesive that protects smoke exit
hole of the smoke cartridge.
12. WORKING LOGIC
www.smarteksrl.it
9. WALK TEST
10. VALIDATION BOARD
The validation card is plugged to the
mother board and must be replaced
together with the smoke capsule
after each use. A flash of the red
LED indicates that the capsule is
not exhausted.
11. COMMISSIONING