BLOWER DATA
EL180UH100NE60C (Less Filter)
External
Bottom Return Air, Side Return Air with Return Air from Both
Static
Sides or Return Air from Bottom and One Side.
Pressure
in. w.g.
High
Med-High
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00
2205 623 1950 415 1710 275 1575 220 1425 160 2235 595 1945 382 1725 262 1590 202 1430 165
0.10
2175 639 1910 427 1685 287 1545 234 1400 176 2205 611 1915 397 1695 280 1550 218 1400 193
0.20
2145 658 1885 449 1635 309 1490 246 1325 181 2165 629 1885 424 1660 293 1510 235 1335 175
0.30
2100 681 1845 466 1605 327 1465 259 1275 196 2135 652 1850 441 1615 312 1475 247 1275 182
0.40
2095 700 1815 481 1565 337 1415 280 1225 204 2085 676 1800 456 1580 330 1430 261 1240 197
0.50
2045 717 1780 499 1525 356 1375 286 1195 218 2055 685 1775 474 1535 347 1395 281 1195 206
0.60
2025 737 1735 516 1500 374 1350 304 1145 230 2025 700 1755 494 1505 359 1355 300 1155 222
0.70
1995 746 1715 533 1465 389 1320 323 1090 248 1990 720 1725 515 1480 377 1310 308 1120 237
0.80
1950 769 1675 547 1430 401 1255 331 1065 259 1965 742 1685 532 1445 396 1275 325 1060 248
Air Volume / Watts at Different Blower Speeds
Medium
Med-Low
Low
Page 4
Single Side Return Air − Air volumes in bold require
Optional Return Air Base and field fabricated transition to
accommodate 20 x 25 x 1 in. air filter in order to maintain
proper air velocity.
High
Med-High
Medium
Med-Low
Low