[8-9 Troubleshooting Problems with Major Components on BC Controller ]
4) Refer to the chart below to judge LEV opening controlled by the values of the differential pressure and of the superheat.
(BC controller LEV basic operation characteristic)
LEV1
LEV3
J, JA, KA
type
LEV4
(JA and KA
types only)
KB type
LEV3
38
- chapter 8
Malfunction
Operation
Part
mode
mode
Inclined to
close
Heating only
Heating-main
Cooling-main
Inclined to
open
Cooling-only
Cooling-main
Inclined to
close
Heating only
Heating-main
Cooling-only
Cooling-main
Inclined to
open
Heating only
Heating-main
Inclined to
Heating-only
close
Heating-main
Cooling-only
Inclined to
Cooling-main
open
Heating-only
Heating-main
Inclined to
Cooling-only
close
Cooling-main
Inclined to
Cooling-only
open
Cooling-main
Standards of judgment on
Content
Difference between high
pressure (P1) and interme-
diate pressure (P3) is large.
Difference between high
pressure (P1) and interme-
diate pressure (P3) is
small.
SH12 is large.
Difference between high
pressure (P1) and interme-
diate pressure (P3) is
small.
SC16 and SH12 are small.
Difference between high
pressure (P1) and interme-
diate pressure (P3) is large.
Difference between high
pressure (P1) and interme-
diate pressure (P3) is
small.
SC16 is small.
Difference between high
pressure (P1) and interme-
diate pressure (P3) is large.
SH12 is large.
SH12 is small.
unit stable operation
0.3 to 0.4MPa
[44 to 58psi]
SH12 < 20°C [36°F]
0.3 to 0.4MPa
[44 to 58psi]
SC16 > 3°C [5.4°F]
SH12 > 3°C [5.4°F]
0.3 to 0.4MPa
[44 to 58psi]
0.3 to 0.4MPa
[44 to 58 psi]
SC16 > 3°C [5.4°F]
0.3 to 0.4MPa
[44 to 58 psi]
SH12 < 20°C [36°F]
SH12 > 3°C [5.4°F]