[5-1 Dipswitch Functions and Factory Settings ]
1)
To change the settings, set SW6-10 to ON, set SW4, and press and hold SWP01 for 2 seconds or longer (OFF ON).
LED3 will light up when the switch setting is ON, and lights off when OFF.
Use the LED3 display to confirm that the settings are properly made.
The settings will need to be set again when the control board is replaced. Write down the settings on the electrical wiring drawing label.
2)
A: OC: Only the switch on OC needs to be set for the setting to be effective.
B: OC: The switches on both the OC and OS need to be set to the same setting for the setting to be effective.
C: OC: The switches on both the OC and OS need to be set.
D: OC: The switch on either the OC or OS needs to be set.
3)
For details, refer to the following page(s).[5-2-7 Defrost Operation Control]
4)
The table below shows how the target evaporation temperature is set with SW4 (982).
SW4(982)
Target evaporating
temperature
5)
Unless otherwise specified, leave the switch to OFF where indicated by "-" or where the cells are blank, which may be set to OFF for a reason.
6)
The settings that are configured with SW4 (SW6-10: ON) will automatically be stored on the indoor units that support the new function*. The stored
settings will automatically be restored when the outdoor unit control board is replaced.
If none of the connected indoor units supports the new function, no configuration information will be saved. If this is the case, manually record the
settings configuration on the control box panel.
*The new function is supported on most units that are manufactured in December of 2012 and later. Depending on the model, this function may be
added on later date. Ask your dealer for further details.
7)
The table below shows the modes selectable with the function switches SW (997) and SW4 (1006).
Switch
SW4(997)
OFF
ON
8)
The table below shows the combinations of the settings for items No. 897 and No. 900 and the target evaporating temperature setting that corresponds
to each combination.
Switch
No.897
OFF
ON
9)
Shaded areas (
) indicate factory settings.
HWE18220_GB
OFF   →   ON   →   OFF   →   ON   →   OFF   →   ON
0
-2
0
-4
[32
]
[28
]
[32
]
[25
SW4(1006)
OFF
50% mode
85% mode
No.900
OFF
0°C [32°F]
6°C [43°F]
0
-6
]
[32
]
[21
]
ON
60% mode
70% mode
ON
9°C [48°F]
14°C [57°F]
5