REQUIRED MAINTENANCE
IMPORTANT:
Per NFPS 96, a signed and
dated VENTILATOR HOOD
MAINTENANCE LOG
must be maintained on the
premises, and be made
available for inspection by the
authority having jurisdiction
upon request.
IMPORTANT:
Should the fire suppression
system discharge, contact
the technical service team:
(800)-264-7827 All lines
and nozzles must be
thoroughly cleaned prior
to recharging the system.
Ansul Deployments are not
covered under warranty.
technical service needs to be
contacted immediately and a
deployment kit of parts needs
to be replaced before unit
is put back in service. WS-
WL0964 Deplymnt kit, WVU/
GK -48
Be sure to note such cleaning
on the hood maintenance log.
Residual fire suppression
media may compromise the
flow and dispersion of fire
suppression media in any
subsequent activation.
USE AND MAINTENANCE SHALL BE IN ACCORDANCE WITH THE
STANDARD FOR VENTILATION CONTROL AND FIRE PROTECTION
OF COMMERIAL COOKING OPERATIONS, N.F.P.A. 96 (current
edition).
3-MONTH MAINTENANCE:
Thoroughly clean entire HOOD PLENUM and BLOWER section.
6-MONTH MAINTENANCE:
Inspection and testing of total operation including FIRE DAMPER and
all SAFETY INTERLOCKS shall be performed by qualified service
personnel.
All FIRE SUPPRESION SYSTEM actuation components including
MANUAL PULL STATION and any REMOTE MANUAL PULL STATION
must be inspected for proper operation in accordance with the
maintenance schedule published in ANSUL® R-102 SYSTEM DESIGN,
INSTALLATION, RECHARGE AND MAINTENANCE MANUAL (418087).
ANNUAL (12-MONTH) MAINTENANCE:
NOZZLES and MANUAL PULL STATION must be cleaned in
accordance with ANSUL® R-102 SYSYTEM DESIGN, INSTALLATION,
RECHARGE AND MAINTENANCE MANUAL (418087).
12-YEAR MAINTENANCE:
The FIRE SUPRESSION AGENT TANK must be HYDROSTATICALLY
TESTED, and the FIRE EXTINGUISHING AGENT must be REPLACED
in accordance with the maintenance schedule published in ANSUL®
R-102 SYSTEM (STANDARD UL 300 LISTED). This maintenance to be
performed by qualified Ansul® service personnel only.
37