Download Print this page

Viconics VRP5000W1000W Manual page 2

24 vac powered zigbee repeater for viconics wireless networks applications

Advertisement

Installation
Remove security screw on the bottom of repeater cover.
Open cover by pulling on the bottom edge of repeater.
Remove assembly and then remove wiring terminals from sticker.
(Fig. 3)
Please note the FCC ID and IC label installed in the cover upon
removal of cover of the wireless products.
A) Installation ( wall or within suspended ceiling ):
1- Swing open the repeater PCB to the left by pressing the PCB
locking tabs. (Fig. 4)
2- Pull cables 6" out of the wall.
3- Mounting surface must be flat and clean.
4- Insert cables in the central hole of the base.
5- Align the base and mark the location of the two mounting holes
on the wall. Install with proper side of base facing up.
6- Install anchors if required.
7- Insert screws in mounting holes on each side of the base.
(Fig. 4)
8- Gently swing back the circuit board on the base and push on it
until the tabs lock.
10- Strip each wire 1/4 inches from end.
11- Insert each wire according to wiring diagram.
13- Gently push excess wiring back into hole (Fig. 5).
14- Re-Install wiring terminals in correct location. (Fig. 5).
15- Reinstall the cover (top side first) and gently push extra wire
length into the hole in the wall.
16- Install security screw.
 Electronic controls are static sensitive devices.
Discharge yourself properly before manipulation and
installing the controller.
 Short circuit or wrong wiring may permanently damage
the controller or the equipment.
Fig.3
Location of PCB retaining tabs
Fig.4
Re-install terminal blocks
Fig.5
Repeater assembly
(VRP5000W)

Advertisement

loading