Viessmann MPA51 Operating And Service Instructions page 9

Gas burner control unit replacement

Advertisement

Burner control unit
Status Service
Status Service
Status Service
Status Service
Status Service
Status Service
Status Service
(cont.)
Quality of the ionisation current
Note
Ionisation current > 50 is very good. If the
value is lower, measure the ionisation
current. The ionisation current should be
> 3 μA. If not, check the ionisation cable
and ionisation electrode.
Start counter with reset, 1 digit
Start counter with reset, 100 digit
Start counter with reset, 1000 digit
Hours run meter with reset, 1 digit
Hours run meter with reset, 100 digit
Hours run meter with reset, 1000 digit
Burner control unit
9