High sensitivity smoke sensor

Advertisement

Available languages

Available languages

TESTING
Sensors must be tested after installation and following periodic
maintenance. Disable the zone or system undergoing maintenance to
prevent unwanted alarms.
Test the sensors as follows:
Magnet Method
1. Test the sensor by positioning the test magnet (model M02-04-00
optional) against the sensor body close to LED 1, indicated by a mark
on the sensor cover as shown in Figure 3.
Figure 3: Test Magnet Position
MARK ON COVER
TEST MAGNET
Both LED's on the sensor should latch into alarm within 30 seconds,
2.
activated by the CIE. To aid positioning, the sensor LEDs will turn on
green for 1s when the alarm switch activates.
Smoke Method
1. Using generated smoke, smoke matches or synthetic aerosol smoke
from an approved manufacturer such as No Climb Products Ltd,
subject the sensor to controlled amounts of smoke in accordance with
local codes of practice and manufacturer recommendations.
2. Both LED's on the sensor should latch into alarm within 30 seconds,
activated by the CIE.
After completion of the test notify the proper authorities that the system is
operational.
LIMITATIONS OF SMOKE SENSORS
These smoke sensors will only work when connected to a compatible
control panel.
Smoke sensors have sensing limitations. They will not sense fires where
smoke does not reach the sensor, and different types of sensor will respond
differently to various smoke types.
Smoke sensors cannot last forever, and we recommend replacement after
10 years.
Honeywell Control Systems Ltd
Honeywell House, Arlington Business Park
Bracknell, Berkshire, RG12 1EB, UK
EN54-7: 2000 / A1: 2002 / A2: 2006 Smoke detectors
EN54-17: 2005 Short Circuit Isolators
Patents Pending
H200-400-00
Honeywell Building Solutions, Honeywell House, Arlington Business Park, Bracknell, Berkshire, RG12 1EB, UK
LED 2
LED 1
0832 19
DOP-IFD203
I56-6298-000