2.6

Circuit-breaker wiring diagram

1)
Only when -Y1 not fitted
2)
External operation
Special arrangement for: -S5
Type 19
– S1 Auxiliary switch on operating mechanism
– S2 Auxiliary switch on blocking magnet
– S3 Auxiliary switch on the breaker shaft
– S4 Auxiliary switch on the breaker shaft
– S5 Auxiliary switch on the breaker shaft
– S7 Auxiliary switch for fault annunciation
(fleeting contact, time ≥ 30 ms)
See page 54 for comparison of VDE/IEC designations.
Shown with the spring energy storage mechanism in the
discharged state. The wiring diagram comprises the
basic components and all further equipment options for
the various VD4 types. The scope of equipment possible
within an individual type series is listed in the relevant
switchgear list, and the equipment fitted in each indivi-
dual case can be found in the order documentation.
Figure 2/15 :
Wiring diagram
Arrangement for DC 24, 48, 60, 110, 125, 220, 240 V; AC 110, 220, 240 V
16
Type 20
Type 22
– Y1 Blocking magnet
– Y2 Shunt release OFF
– Y3 Shunt release ON
– Y4 Undervoltage release
– Y7 Indirect overcurrent release
– Y9 Second shunt release OFF
– V1 Series rectifier for – Y1
– V2 Series rectifier for – Y2
Type 23
– V3 Series rectifier for – Y3 and – K0
– V4 Series rectifier for – Y4
– V9 Series rectifier for – Y9
– M0 Charging motor for spring
energy store
– K0 Anti-pumping relay
– R0 Series resistor
Note:
Shunt releases and blocking magnets are fundamentally
wired with rectifiers (e.g. magnet holder 40 with integrated
rectifiers -V1, -V2, -V3 and -V9).
Rectifiers function as free-wheeling diodes if d.c.-supply.
Standard
arrangement
Type 21
Type 24