Dip Switch And Dip Switch Settings - Haier AW09ES2VHB Service Manual

Table of Contents

Advertisement

Available languages

Available languages

DIP Switch
DIP Switch Settings
The PCB for the indoor unit of the Advanced series of single
zone mini-splits has a set of DIP switches that must be set
when replacing the PCB.
The replacement PCB is shipped with all switches set to the
OFF position.
Switch settings:
SW2-1 Selects remote code A or B. Normally set to the off
position for code A operation.
If two indoor units are used in the same area and the user
wishes to control them separately, switch SW2-1 of the
second unit is set to the ON position for code B operation.
The wireless remote for the second unit is also set to code B.
SW2-2 Selects room card enable or disable.
Normally set to the OFF position. Set to the ON position
when used in conjunction with a room card interface utilized
in hotel rooms.
SW-3 & SW-4 Selects eeprom code 23, 26, 33 and 35. Set to
identify the tonnage of the unit.
Settings:
9K
(23)
SW-3
12K
(26)
SW-3
15K
(33)
SW-3
18K
(33)
SW-3
24K
(35)
SW-3
PAGE 20
OFF
SW-4
OFF
OFF
SW-4
ON
ON
SW-4
OFF
ON
SW-4
OFF
ON
SW-4
ON
INDOOR UNIT CONTROLS & COMPONENTS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents