SEQUENCE OF OPERATION
The setting
of the system
switch
on the room
thermostat
controls the operation
of the unit heat-
ing or cooling
cycles. Once the system
switch is
placed
either in the "HEAT" or "COOL"
position,
unit operation
is automatic.
A fan switch on the
thermostat
also provides for continuous
operation
of the evaporator
fan when desired. The fan switch
"ON" position provides continuous
operation while
the "AUTO" position provides operation during the
heating or cooling cycles.
HEATING
CYCLE
On a call for heat by the room thermostat,
the
control
module
(IGN) runs its self-check
routine.
After the control
has verified
that the pressure
switch
(PS) contacts
are open,
the limit switch
(TCO) contacts
are closed, and the flame rollout
(FL) switch
is closed, the combustion
fan motor
(CFM) will be energized.
As the combustion
fan motor (CFM) comes up to
speed, the pressure switch (PS) contacts will close.
After approximately
20 seconds,
for the combus-
tion fan motor (CFM) prepurge, the gas valve (GV)
is energized
permitting
gas flow to the burners.
Concurrently,
the spark ignitor (IP) is energized.
The flame detector
(FD) confirms that ignition has
been achieved within the seven second trial period.
Upon proof of ignition,
the delay to indoor fan on
period begins
timing and after approximately
45
seconds,
the indoor
blower
motor (IDM) will be
energized
and will continue to run during the heat-
ing cycle.
When the thermostat
is satisfied,
the gas valve
(GV) will close and the flame will extinguish.
The
combustion
fan motor (CFM) will continue to run for
a postpurge
period of approximately
5 seconds
then will be de-energized.
The indoor blower motor
(IDM) will continue to run for the fan off period (field
selectable
60 or 90 seconds
(by jumpers),
then will
be de-energized
by the control module.
SAFETY
SEQUENCES
AND LIMIT CONTROLS
During the main burner operation,
if gas is inter-
rupted or discontinued,
the gas valve (GV) is de-
energized
instantly.
The ignition
control
module
(IGN) then enters the retry mode. The retry mode
allows the control (IGN) to purge for 60 seconds.
Following
this time period the valve is energized
and the spark is started. If the flame is not sensed
by the flame detector
(FD) within 7 seconds
the
valve is de-energized
and the spark is stopped.
A second retry is then attempted.
If this attempt at
ignition
is unsuccessful,
a third retry will be at-
tempted
after a prepurge
period.
If this third at-
tempt at ignition
is unsuccessful,
the control will
lock out. It can be reset by removing
power to the
unit or by turning the thermostat
from "on" to "off" for
approximately
three seconds, then back "on 2 If not
reset, the control module will automatically
reset in
1 hour.
The temperature
limit switch (TCO) protects against
overheating
if the indoor motor (IDM) fails to oper-
ate. Also, a fusible link (FS) protects against flame
rollout due to flue blockage.
These switches
will
interrupt the operation
of the unit by de-energizing
the ignition
control
module
(IGM) if overheating
OGCU rs.
The temperature
limit switch (TCO) is located in the
gas compartment.
This
automatic
reset
device
protects
against
excessive
leaving
air tempera-
ture.
The fusible link (FS) is located in the gas compart-
ment near the burners. This is a single use device
designed
to protect
against
any form of flame
rollout.
COOLING
CYCLE
With the room thermostat
system
switch
in the
"COOLING"
position
and the fan switch
in the
"AUTO"
position,
the compressor
contactor
(CC)
and the indoor fan relay (F) are energized.
The energized
compressor
contactor
(CC) com-
pletes the circuit to the compressor
(CPR) and a
secondary
circuit to the outdoor fan motor (ODM).
If the compressor
safety controls
are closed, the
compressor
(CPR) will operate with the outdoor fan
motor
(ODM).
The indoor
fan motor
(IDM) will
operate. The thermostat
will continue
to cycle the
compressor
and fans to maintain the desired tem-
perature.
With the thermostat
fan switch in the "ON" posi-
tion, the indoor fan motor (IDM) will continue
to
run regardless
of compressor
and condenser
fan
operation.
Page 20