FILTER iNSTALLATiON
AIR FILTERS
TABLE
4
Filters are to be used with the YCP024=060F heating/cooling
units.
The basic unit does not have filters in it. However, a filter frame
accessory is offered that will allow filters to be installed within the
unit.
Otherwise a filter rack must be installed by the installer in the duct
work,
Affix the filter label supplied with the unit adjacent to the filter area.
*Filters must be installed
in the return air system.
The above square
footages are based on 300 F.PM. face velocity.
If permanent
filters are
used, size per mfg. recommendation
with clear resistance
of 0.05" WC.
NOMINAL
FILTER*
FILTER
UNIT
CFM
Sq.Ft.- SIZE
RESISTANCE
YC~018F/G
600
ZOO
0.05
YC~024F/G
800
2.67
0.05
YC~030F/G
1000
3.33
0.05
YC~036F/G
1200
4
0.05
YC~042F/G
1400
4.67
0.05
YC~048F/G
1600
5.33
0.05
YC~060F/G
2000
6.67
0.05
ELECTRICAL
WIRING
ELECTRICAL
CONNECTIONS
Electrical wiring and grounding must be installed in accordance with
local codes or, in the absence of local codes, with the National
Electrical Code ANSI/NFPA
70, Latest Revision.
ELECTRICAL
POWER
It is important that proper electrical power be available for the unit.
Voltage variation should remain within the limits stamped on the unit
nameplate.
DISCONNECT SWITCH
Provide an approved weatherproof disconnect either on the side of
the unit or within close proximity and within
sight of the unit.
OVER CURRENTPROTECTION
The branch circuit feeding the unit must be protected as shown on
the unit rating plate.
POWER WIRING
The power supply lines must be run in weathertight
conduit to the
disconnect and into the bottom of the unit control box. Provide strain
relief for all conduit with suitable connectors.
Provide flexible conduit supports whenever vibration transmission
may cause a noise problem within the building structure.
Be sure all connections are made tight. See Figure 18.
NOTES: For branch circuit wiring (main power supply to unit
disconnect), wire size forthe length of run should be determined
using the circuit ampacity found on the unit nameplate and the
N.E.C.
For more than 3 conductors in a raceway or cable, see the
N_
acit
of each conductor.
GROUNDING: THE UNITMUST BE ELECTRICALLYGROUNDED
IN ACCORDANCE
WITH LOCAL CODES OR THE NATIONAL
ELECTRIC CODE.
NOTE: Unit must be grounded for ignitor to operate prop-
erly. Gas pipe to unit is not an adequate ground. Ground
the unit internally
as provided.
See wiring diagram for
location.
COMPRESSOR
MOTOR
ROTATION
DISCONNECT
ALL POWERTO
COMPRESSORWHEN
COMPRESSOR
MOTOR ROTATION IS REVERSED. CHANGE
ANYTWO
CUSTOMER
POWER LEADS TO CORRECT
ROTATION
Failure to change customer
power leads to correct
compressor
rotation may result in compressor
damage
during
operation.
CONTROL WIRING (CLASS II)
Low voltage control wiring should not be run in conduit with power
wiring unless Class 1 wire of proper voltage rating is used. Route
the thermostat cable or equivalent
single leads of No. 18 AWG
colored wire from the thermostat
subbase terminals through the
rubber gromment on the unit. See Figures 3 and 4 for the control
entry location.
Make connections
as shown on the unit wiring
diagram and in Figure 18.
Do not short thermostat wires since this wilt damage the control
transformer.
Recommended wire sizes and lengths for installing the unit thermo-
stat are provided in Table 5. The total resistance
of these low
voltage wires must not exceed one (1) ohm. Any resistance
in
excess of 1 ohm may cause the control to malfunction because of
the excessive voltage drop.
TABLE
5
THERMOSTAT
WIRE SIZE AND MAXIMUM LENGTH
WIRE SIZE
MAXIMUM LENTGH (Ft)
18
75
16
125
14
200