2. Loosen the 6 screws on front cover (fascia)
using a posidrive screw driver as shown in Fig 1.B
Rotate the charging handle down and slide the
front cover over the handle to remove the front
cover as shown in Fig. 1.C.
Figure 1. (B) Screw Removal (C) Handle Rotation
3. If the locking mechanism device has been
supplied factory fitted, remove the bracket and
cover from the EntelliGuard device. If supplied as
a field mountable kit, please proceed to step 4.
4. Take the Lock cover and carefully break out the
openings needed to place the required number of
locks
5. Fix each lock to the lock bracket using the
fixation nuts as indicated in Fig. 2
Figure 2.
6. Using the nut supplied with each lock fix the
activating CAM. Ensure that the CAM is positioned
as indicated in fig. 3. For Kirk Lock, insert the
spacer and fix the cam supplied with the Kit using
the screws provided in the lock.
Ronis lock
Profalux lock
Kirk lock
Figure 3.
7. Using the supplied screws fit the cover onto the
mechanism.