HS-3100/3200 Programming Manual
Alarm List
This menu controls the operation of the Alarm List. This function is restricted to Privilege Level 2. It
has the following options:
Passcode
Allows for the changing of passcodes. The Privilege Level 2 can change both the Level 1 and 2
passcodes, while Level 1 can only change the Level 1 passcode. Passcodes are four digit
numbers in the range 1000 to 9999. Type in the new passcode and press <Enter> to accept.
Asterisks are displayed instead of the numbers. <Clear> removes any digits typed. If no digits are
displayed, <Clear> returns to the Program or Passcode Menu.
The default Level 2 passcode is 2222. The default Level 1 passcode is 1111. These passcodes
should be changed to prevent unauthorized access.
There is a special Level 2 passcode that is variable from day to day. It can be obtained from
Harrington if the Level 2 passcode is forgotten.
Memory
This function is restricted to Privilege Level 2. This menu has the following options:
42
Port 6: Allows for the setting of the baud rate to HS-3434 and HS-3644 annunciators, the
city tie modules, and the HS3DL dialer. The settings are 4800 and 1200. If none of these
devices are programmed in the database, the message "nothing to program" is shown.
Reset: Select when entries are taken out of the Alarm List. AUTO removes entries as
soon as the condition restores. MANUAL requires that Reset be pressed before they are
removed. Conditions that have restored are shown as a restored condition in the Alarm
List.
Remote: Routes the messages for events from the panel to annunciators. The options
are:
-- ALL: All messages are sent to all annunciators.
-- SELECT: Messages are sent as directed in the database.
Erase Configuration: This erases all initiating circuit, bell, relay, and privilege values
entered from the keypad and LCD menu, and replace them with default values. With HS2
programs, this has no effect on information contained in the downloaded database.
Confirmation is asked before erasure. After the Configuration has been erased, the panel
must be reset using the reset button at the top of the Main Circuit Board, if the panel does
not do this automatically. The following items are not erased: Serial Number, Clock
Calibration, Level 1 Passcode, Level 2 Passcode, Main Board Type, Input Circuit
Modules.