2.6 Panel Window

Overview
The Panel Window (see Figure 5) allows editing of all panel level options. It defines the hardware
mounted in the panel and the functionality of the programmable outputs. The programming
controls provided change to reflect the capabilities of the currently selected panel. The Title Bar
describes the currently highlighted panel or annunciator.
Figure 5: Panel Window
Note:
This can have far reaching effects on a system. Any information that is no longer valid with the
new panel type will be lost
14
Exit: Close the Panel Window and return to the System Window.
Add Panel: Add another panel to the system. A dialog box will be displayed. The default
options are to use the next available panel ID and to select an HS-3030 panel . You will
also be asked if you want NP to automatically set the Next ID. If allowed, this panel will
have the next higher numbered panel as its Next ID and the panel with the next lower
number will be set to have this panel as its Next ID. If the new panel is the highest
numbered panel, it will use the lowest numbered panel as its Next ID.
Delete: Remove the current panel from the system. All programming for that panel will be
lost. Any of the panel's outputs that are referenced will become invalid and will be
removed by the next verify.
Input Circuits: Display the Circuits Window. See section 2.6
Internal Circuits: Display the Internal Circuit Window. See section 2.7.
More Info: This displays a dialog box listing basic information about the panel including
the date the database was last downloaded into a panel, the number of times downloaded,
etc.
Change Type: Displays a dialog box to change the type of the current panel. This makes
it easier to correct mistakes when creating a database and to update the database if a
panel type is changed in the field. Only certain type changes are allowed.
Change ID: Displays a dialog box for changing the ID of the current panel. NP will
automatically change all references to use the new ID. This process could take a long time
for a large database. A gauge will be displayed to show the progress of the change.