Side Flue Option: - Bosch Worcester Greenstar Oilfit External Installation Instructions Manual

External flue kit, low level horizontal balanced flue
Table of Contents

Advertisement

INSTALLATION
4.3

SIDE FLUE OPTION:

DANESMOOR (2013) AND HEATSLAVE II
To use the right hand or left hand flue options a 90°
swept flue elbow is required (part no. 7 716 190 034)
Lightly grease the 90° flue elbow seals with the solvent
free grease.
DANESMOOR (2013) AND HEATSLAVE II FLUE OPTIONS
80mmØ flue pipe length L in mm
Boiler
Danesmoor (2013) Heatslave II
Flue outlet
Right hand
240*
Left hand
255*
Table 2 Flue pipe lengths
[*]
Danesmoor (2013) and Heatslave II righthand flue:
the 125mm air inlet outer section is not needed for these outlet
position and so there will be one screw spare.
[**]
Heatslave II lefthand flue:
Use both inner and outer air inlet sections,
but cut the outer section down to 150mm.
▶ Cut the 80mm flue pipe as required, see table 2
▶ Fit the air inlet section [2] to the elbow [3].
▶ Fit the clamp [1] to the flue cowl.
Fig. 8
[1]
Flue clamp
[2]
Flue section
▶ Push the air inlet section through the side panel opening into the air
box until it meets the stops [4] on the clamp assembly
▶ Centralise the inner elbow pipe within the elbow.
▶ Fit the elbow [3] onto the flue cowl.
▶ Tighten the clamp [1] onto the flue elbow.
6
230*
340**
1
2a
2b
&
6720807912-11.1Wo
1
3
Fig. 9
[3]
Elbow
[4]
Clamp stops
[5]
Clamp
▶ Drill through the tab [6] on the mounting bracket, with the 3.3mm
drill bit into the air inlet outer section and secure with a self-tapping
screw.
Fig. 10 Tab detail
4
5
6720807912-12.1Wo
3.3mmØ
6
6720807912-13.1Wo
6 720 807 912 (2015/10)

Advertisement

Table of Contents
loading

Table of Contents