Download Print this page

Product Specifications - Philips dynalite DUS360CR Quick Start Manual

Low profile 360 ceiling sensor

Advertisement

Installation Steps
1.
Install the sensor into a 64 mm wide round hole in a firm section of the ceiling. The mounting position should adhere to the following:
Ceiling height should be between 2.1 m and 4.0 m. Optimum height is 2.4 m.
Position the sensor at least 1 m away from electrical lighting such as neon and fluorescent lights.
Avoid exposure to direct sunlight and heating/cooling sources.
Position the sensor where pedestrian traffic is likely to move through the detection zone.
Note that the sensor coverage area is rectangular, approximately 7.6 m x 5.4 m (at 2.4 m installation height).
The detection range above is specified for an ambient temperature of 25ºC. This range is reduced at higher temperatures.
2.
If needed, pull out and rotate the PIR shield to block a 120º viewing angle.
3.
DUS360CR-DA ONLY: Set the device's Area, Timeout and Corridor Hold ON feature using the DIP switches as detailed below and on the
device label. If using Corridor Hold ON feature, enable this option on only one sensor in the designated corridor Area.
4.
Terminate the DyNet cable as indicated below. If using the dual-socket RJ12 or RJ45 connector, follow the pinout shown.
If terminated and powered correctly, the red indicator LED turns on for 5 seconds.
RS485 DyNet network
Daisy chained
device

Product Specifications

DyNet Terminal
5-way pluggable screw terminal
1 x 2.5mm
DyNet Network Supply
RS485 12-24 VDC, 20mA max
PIR sensor:
Quad element pyroelectric
Max detection range:
5 m
Detection area:
7.4 m x 5.6 m (at 2.4m mounting height)
Detection speed:
1 m/s
Detection object:
700 mm x 250 mm
Detection zones:
64
Activation indicator:
Red LED
PE cell:
<5 to >5000 lux (reflected)
Automatic daylight harvesting mode
Controls:
DIP switch (DUS360CR-DA only)
Service switch
Infrared receiver (supports RC5)
Compliance:
cULus, CE, RCM, FCC, ICES-003
Operating Conditions:
Temperature: 0 to 45° C ambient
Humidity: 0 to 90% non-condensing
Storage & Transport:
Temperature: -25 to 70° C ambient
Humidity: 0 to 90% non-condensing
Construction:
Polycarbonate plastic enclosure
Dimensions:
72 mm dia. x 41 mm (2.8" dia. x 1.6")
Packed Weight:
105 g
Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
Recommended Cable Type
Dynalite DYNET-STP-CABLE or equivalent
shielded four twisted-pair cable.
See the DYNET-STP-CABLE datasheet for more
information.
Shield
Green/Green white
Blue
Blue white
Orange/Orange white
Brown/Brown white
First or last device
conductor size
2
DUS360CR Installation Instructions Rev 02 Specifications subject to change without notice
E-Mail: support.controls@philips.com
Recommended Cable Color Coding
Green/White Pair
Orange/White Pair
Blue/White Pair
Brown/White Pair
DIP Switch Area Selection Table
5
4
1
2
On
3
Off
4
5
6
7
8
9
10
11
12
13
14
15
16
Web: http://philips.com/dynalite
RJ12 socket
Paralleled for GND
Paralleled for +V (12-24 VDC)
Blue for DATA+
White for DATA-
Spare
3
2
1
5
4
17
18
19
20
21
22
23
24
25
26
27
28
29
30