6.

Detection coverage

Area optics with sneak-by guard
Depending on the detector application, the mirror optics can be exchanged on site. The following mirror sets are available for this purpose: Long-
range optics and Curtain optics. Details see Chapter 15.2 "Viewguard PIR mirror sets".
Optics
Lens splitting
22 zones at 5 levels
Opening angle
80° hor., 64° vert.
Range
8 / 11 / 13 / 15 m
Mounting height
Recommended
:
2.50 m
for optimal operating sensitivity.
Permitted:
2.20 m to 3.40 m
ATTENTION!
Important note for mounting heights of more than 3.00 m:
In case of mounting heights of 3.00 to 3.40 m, the close range
between 0 - 1.50 m cannot be monitored completely despite the
requirements for VdS systems (see detection coverage
diagram on right side).
Please inform the operating company and insurers about this
fact.
As the case may be, the respective areas must be monitored
separately by appropriate means (such as a second detector).
Detection diagrams
The following diagrams refer to a
Mounting height 2.50 m
(2.20 m to 3.00 m)
Vertical inclination:
- up to 2.80 m:
- from 2.80 m:
optional 3° downward
verify by
Horizonal detection coverage
9m
6m
3m
0
3m
6m
Expected
direction
of motion
9m
0
3m
6m
Fig. 3
Vertical detection coverage
2.5m
0m
3m
6m
Fig. 4
(state of delivery)
range setting of 15 m
.
walk test
40°
30°
20°
10°
10°
20°
30°
40°
9m
12m
9m
12m
Mounting and Connection Instructions Viewguard PIR RF
Mounting height 3.00 to 3.40 m
Vertical mounting inclination 3° downward.
Mounting as per Fig. 8/2
Horizonal detection coverage
6m
3m
0
3m
6m
Fig. 5
0
Vertical detection coverage
3.2m
Fig. 6
0
7.
Housing
-
Open housing
1
If necessary, break the seal with a
small screwdriver or similar object and
pull downward.
2
Press the notch (at the bottom in the
middle, see Fig. 1- ) slightly inward.
3
Press off the front of the housing.
4
Lift off the housing front.
-
Close housing
in reverse order. Ensure that the housing
is closed correctly and locked into
position.
15m
Do not insert the seal to lock the housing
until installation is completed.
Fig. 7
15m
40°
Expected
direction
of motion
40°
3m
6m
9m
3m
6m
9m
30°
20°
10°
10°
20°
30°
12m