Installing Cables; Installation Preparations - Huawei SUN2000-50KTL-M0 Quick Manual

Hide thumbs Also See for SUN2000-50KTL-M0:
Table of Contents

Advertisement

4

Installing Cables

Installation Preparations

4.1
NOTE
Before installing cables, ensure that all required OT terminals and cables are prepared.
The following table lists only recommended cable specifications. For more cable specifications,
see the user manual.
No.
Name
1
Ground cable
AC output power
2
cable
3
OT terminal
4
DC input power cable
RS485
communications cable
(terminal block)
5
RS485
communications cable
(RJ45 network port)
Solar tracker power
6
cable (optional)
Cable tie
7
Model/
Specifications
2
16 mm
outdoor copper
cable
2
35 mm
outdoor copper
cable
M8
M10
PV cable that meets the
1100 V standard
Communications cable with
a conductor cross-sectional
2
area of 1 mm
and outer
diameter of 14–18 mm
CAT 5E outdoor shielded
network cable with an outer
diameter less than 9 mm
and internal resistance not
greater than 1.5 ohms/10 m,
as well as shielded RJ45
connectors
Dual-layer three-core
outdoor copper cable with a
conductor cross-sectional
2
area of 10 mm
N/A
5
Description
If you choose the ground point on
the enclosure for connecting a
ground cable, prepare the ground
cable.
If you choose the ground point in
the maintenance compartment for
connecting a ground cable, use an
AC output cable that includes a
ground cable instead of preparing
an extra ground cable.
N/A
When using outdoor copper cables for
AC connection, select copper wiring
terminals. For requirements on the
cables and terminals of other
materials, see the user manual.
N/A
If RS485 communication is used,
prepare the RS485
communications cable.
A terminal block is recommended
for connecting the RS485
communications cable.
N/A