5. End of operation

After filling and flushing the solar system
> Switch off pump.
> Close fill and vent valve (1+2) at the solar
station.
> Open stop valve (3) between fill and vent valve.
The pressure that is generated between pump outlet
and fill valve when flushing the pipe can be released
by opening the filter at the pump inlet. It will be easier
then to unscrew the filling hose from the fill valve.
Caution: Collect escaping pumped media in a
container.
> Unscrew the filter casing and flush remaining liquid.
> Unscrew the filling hose from the fill valve.
> Unscrew return hose from vent valve.
> Screw open hose ends together with the provided connecting piece in order to
avoid dripping or escaping of fluid during transport.
ZUWA SOLARCHECK MOBILCENTER english
7.
Open tank lid to ensure the circulation
of the air.
Caution: Monitor fluid level in the tank and,
if necessary, refill heat transfer fluid to
prevent air entering the solar circuit.
8.
Flush the solar circuit with the fluid.
Check at the inspection window of the
filter or through the tank opening if
there are still air bubbles in the heat
transfer fluid. Continue flushing until
there is no air remaining in the fluid.