Viessmann Vitodens 200-W Series Installation And Service Instructions Manual page 67

Wall mounted
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
A9:7
With pump idle time: Heating cir-
cuit pump "OFF" if the set value is
altered through a change in oper-
ating mode or through a change in
the set room temperature (only for
weather-compensated control
units)
b0:0
With remote control: Heating
mode/reduced mode: weather-
compensated (only for weather-
compensated control units; only
change the code for the heating
circuit with mixer)
b2:8
With remote control and for the
heating circuit, operation with room
temperature hook-up must be pro-
grammed: Room influence factor 8
(only for weather-compensated
control units; only change the code
for the heating circuit with mixer)
b5:0
With remote control: No room tem-
perature-dependent heating circuit
pump logic function (only for
weather-compensated control
units; only change the code for the
heating circuit with mixer)
Parameter address
With heating circuit pump logic function:
b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only for weather-
compensated control units)
C6:74
Electronic maximum flow tempera-
ture limited to 74 °C (only for
weather-compensated control
units)
d3:14
Heating curve slope = 1.4
RT
+ 5 K
>
actual
set
RT
+ 4 K
>
actual
set
RT
+ 3 K
>
actual
set
RT
+ 2 K
>
actual
set
RT
+ 1 K
>
actual
set
RT
>
actual
set
RT
- 1 K
>
actual
set
RT
- 2 K
>
actual
set
(cont.)
Possible change
A9:0
Without pump idle time
A9:1
With pump idle time, adjustable from
to
1 to 15. The higher the value, the
A9:15
longer the pump idle time.
b0:1
Heating mode: weather-compensa-
ted
Reduced mode: with room tempera-
ture hook-up
b0:2
Heating mode: with room tempera-
ture hook-up
Reduced mode: weather-compensa-
ted
b0:3
Heating mode/reduced mode: with
room temperature hook-up
b2:0
Without room influence
b2:1
Room influence factor adjustable
to
from 1 to 64. The higher the value,
b2:64
the greater the room influence.
b5:1
For heating circuit pump logic func-
to
tion, see the following table:
b5:8
Heating circuit pump "ON"
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
Possible change
C5:1
Minimum limit adjustable from 1 to
to
127 °C (limited by boiler-specific pa-
C5:127
rameters)
C6:10
Maximum limit adjustable from 10 to
to
127 °C (limited by boiler-specific pa-
C6:127
rameters)
d3:2
Heating curve slope adjustable from
to
0.2 to 3.5 (see page 40)
Code 2
+ 4 K
+ 3 K
+ 2 K
+ 1 K
- 1 K
- 2 K
- 3 K
67