Trane Horizon OAB Series Installation, Operation And Maintenance Manual page 28

Outdoor air unit, direct gas-fired
Table of Contents

Advertisement

System Configuration and Pre-Start
Table 5.
Menu descriptions (continued)
Screen
Menu
System Setpoints
Reports
(continued
from
previous
page)
System Setup
Override Summary List of active overrides - same as selecting Override button at top of screen
All Point Report
About
Expansion Modules Provides status of expansion modules
TGP2 Programs
Data Graphs *NOT USED*
Schedules - Refer to UC600 IOM for scheduling functions
Display Preferences
Settings
Language
Date and Time
Clean Touchscreen
28
Point List
DAT High Temp Cutout
DAT Low Temp Cutout
DAT Temp Cutout Time
Discharge Air Cooling Setpoint
Discharge Air Heating Setpoint
EVAP Leaving Temp Setpoint
IVFD Signal
Maximum Discharge Air Temperature
Minimum Discharge Air Cooling Setpoint 40°F
Minimum Discharge Air Heating Setpoint 50°F
Maximum OA Damper Position
Minimum OA Damper Position
Occupied Space Cooling Setpoint
Occupied Space Heating Setpoint
Outdoor Air Cooling Setpoint (OACS)
Outdoor Air Dewpoint Setpoint (OADS)
Outdoor Air Heating Setpoint (OAHS)
Space Dewpoint Setpoint (SPDS)
UNOCC Space Cooling Setpoint
UNOCC Space Dewpoint Setpoint
UNOCC Space Heating Setpoint
Program Control
Compressor Count
Heater Count
Split Manifold Burner
Return Air Damper Option
Space Temp/Humidity Sensor Installed
Heat Type
Alarm Reset
Supply Fan Failure Reset
List of all points (AO/AI/BO/BI/MS/etc ...) in the configuration file
Controller Name listed is the version of the program installed in the UC600
List of all TGP2 programs loaded on the UC600
Min/Inactive
Default
100°F
125°F
35°F
35°F
10 min.
10 min.
55°F
55°F
65°F
85°F
45°F
53°F
50%
100%
70°F
90°F
50°F
55°F
0%
100%
0%
100%
65°F
74°F
60°F
70°F
70°F
75°F
49°F
58°F
40°F
70°F
50°F
59°F
60°F
80°F
49°F
65°F
50°F
60°F
Discharge Air Control Space Control
0
0
0
0
Not Installed
Installed
Not Installed
Installed
Not Installed
Installed
No Heat|Gas Heat|Electric Heat|Other
Off
Off
Off
Off
BAS
Max/Active
Point?
150°F
Y
50°F
Y
25 min.
Y
75°F
Y
90°F
Y
70°F
Y
100%
Y
100°F
Y
65°F
Y
60°F
Y
100%
Y
100%
Y
90°F
Y
75°F
Y
85°F
Y
65°F
Y
70°F
Y
68°F
Y
90°F
Y
68°F
Y
70°F
Y
Space Control
Y
4
N
2
N
Installed
N
Installed
N
Installed
N
N
On
Y
On
Y
OAU-SVX005C-EN