Step 12 Insulating the refrigerant
pipes
Once you have checked that there are no leaks in the
system, you can insulate the piping and hose.
22
English
Drain cap (5EA)
Drain plug (1EA)
060/071
Drain cap (4EA)
Drain plug (1EA)
Drain plug (1EA)
1 To avoid condensation problems, place an insulator
around each refrigerant pipe.
No gap
NBR
NOTE
• When insulate the pipe, be sure to overlap the
insulation.
• The insulation has to be produced in full compliance
of European regulation reg. EEC / EU 2037/ 2000
that requires the use of sheaths insulation form
without using CFC and HCFC gases for health and the
environment.
CAUTION
• When insulating the pipe, use non-slit insulator.
2 Select the insulation of the refrigerant pipe.
• Insulate the gas side and liquid side pipe referring
to the thickness according to the pipe size.
• Less than Indoor temperature of 30°C and
humidity of 85% is the standard condition. If
installing in a high humidity condition, use one
grade thicker insulator by referring to the table
below. If installing in an unfavourable conditions,
use thicker one.
• Insulator's heat-resistance temperature should be
more than 120°C.
Standard
Pipe
Pipe size
[Less than
30°C, 85%]
Ø6.35~Ø9.52
Liquid pipe
Ø12.7~Ø19.05
Ø6.35
Gas pipe
Ø9.52~Ø19.05
• When installing insulation in places and conditions
below, use the same insulation that is used for
Insulation Type
(Heating/Cooling)
High
humidity
Remarks
[over 30°C,
85%]
EPDM, NBR
9 t
9 t
Internal
13 t
13 t
temperature
is higher than
13 t
19 t
120°C
19 t
25 t