18 | ACS 151 | Maintenance
7.5

Replacing the inline filters

The inline filters have to be changed every time the fil-
ter drier is changed. The inline filters are housed in the
adapters (Fig. 10, Pos. 1).
1
459897_117Nkv
Fig. 10:
Inline filter overview
1. Adapter
2. Filter insert
3. Adapter for hoses
4. O-ring
1. Perform hose drain (see chapter 6.3.2).
2. Switch off the master switch.
3. Disconnect the power cable from the mains supply.
4. Disconnect the hoses from the connectors.
5. Execute steps 9 to 12 from chapter 7.4.
6. Fasten the hose connectors back.
7. Connect the HP and LP hoses to the hose connec-
tors.
"
You have successfully replaced the inline filters.
7.6

Purging non-condensable gases

1. Open the left panel.
2. Pull the ring mounted on the Y-valve of the refriger-
ant tank.
3. Release the ring once the NCGs are released.
4. Close the left panel.
|
F 002 DG9 448
2018-02-01
3
2
4
8.

Decommissioning

8.1

Disposal of electronic items

This product is subject to European guidelines
2002/96/EG (WEEE).
Old electrical and electronic devices, including
cables and accessories or batteries must be
disposed of separate to household waste.
Please use the return and collection systems
in place for disposal in your area.
Damage to the environment and hazards to
personal health can be prevented by prop-
erly disposing of old equipment.
8.2
Disposal of LCD, refrigerants, lubri-
cants and oils
Please dispose of the LCD display in accordance with
the local regulations for disposal of special waste.
Refrigerants that can no longer be used must be hand-
ed over to the gas suppliers for disposal.
The lubricants and oils recovered from the A/C systems
must be disposed in accordance with local regulations.
8.3

Disposal of filter drier

Dispose the filter drier through the designated return
points or in accordance with local regulations.
9.

Technical data

Property
Value/Range
Operating voltage
230 V ± 10 %
Frequency
50 Hz
Refrigerant
R134a
R134a scale
50 kg
LP manometer
-1 bar - 15 bar ± 1.6 % of final value
HP manometer
-1 bar - 34 bar ± 1.6 % of final value
Refrigerant tank capacity 12 l
Maximum system pres-
20 bar
sure PS
Pset
18 bar
Medium group
Group 2
Power
Permissible ambient tem-
10
perature TS
Optimum filling weight of
4 kg - 7 kg
R134a for operation
Dimensions (H x W x D)
1020 x 530 x 610
(mm)
Weight
75 kg
C - 50
C
O
O