1. Wiring cable size must comply with the applicable local and national codes. And "Electric characteristics" chapter should be considered for
electricalwork and design. Especially the power cable and circuit breaker should be selected in accordance with that.
2. The guideline about cable is taken into account laying B2 from the table A.52.4 – IEC 60364-5-52. The cable in the installation pipe is fixed to the wall.
3. The size of Electrical Heater and the Fuses depend on the choice of the connection power.
4. Joint maximal load (circulation pumps, electronic valves ...) which can be connected to or powered by the internal unit, must not exceed the
specifiedvalue. Higher consumed parts (i.e. pumps) should have their own supply.