Invert 00.00 19.27 Relay state 19.17 RL3O Output relay 3 RL3C Source RL3F 19.38 Invert 00.00 19.28 Relay state 19.18 RL4O Output relay 4 RL4C RL4F MDX-I/O M2M Additional Input/Output module with Datalogger function POWERDRIVE MD2/FX Installation and commissioning manual...
Page 2
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function NOTE LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate the latest technological developments. The information contained in this document is therefore liable to be changed without notice.
Page 3
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function SAFETY AND OPERATING INSTRUCTIONS FOR VARIABLE SPEED DRIVES (in accordance with the low voltage directive 2006/95/EC) 2 - Use • Throughout the manual this symbol...
Page 4
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function 4 - Installation 6 - Operation The installation and cooling of equipment Installations which incorporate variable speed must comply with the specifications in the drives must be fitted with additional protection documentation supplied with the product.
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional I/O module with Datalogger function CONTENTS CONTENTS 1 - GENERAL INFORMATION ................. 6 1.1 - General ........................6 1.2 - Dimensions ........................6 2 - INSTALLATION ....................7 3 - CONNECTIONS AND CHARACTERISTICS ............
GENERAL INFORMATION 1 - GENERAL INFORMATION 1.1 - General The MDX-I/O M2M module is used to increase the number of drive Input/Output and also has a Datalogger function. This option is fully configurable. Details of functions: - 2 analog inputs (including a differential analog input)
5 - If you wish, an additional option module can be added (e.g. MDX-ENCODER). Remove the black plastic protective cover on the MDX-I/O M2M, undo the screws inserted in step 4. Align the additional option module over the MDX-I/O M2M board connector (the additional module connector is located on the underside of the casing) then press gently until it is fully in place.
10 minutes after powering down). For the safety instructions relating to the drive, please refer to the manual supplied with the product. • The inputs on the POWERDRIVE MD2 and MDX-I/O M2M board have a positive logic configuration. Using a drive with a control system which has a different control logic may cause unwanted starting of the motor.
Page 9
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function CONNECTIONS AND CHARACTERISTICS Voltage mode Full scale voltage range ± 10V ± 2% Maximum voltage 27 V Absolute maximum voltage 33 V...
Page 10
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function CONNECTIONS AND CHARACTERISTICS Digital output 2 Digital output 3 Factory setting No assignment Type Open collector Absolute maximum voltage +30 V/0 V...
Inappropriate settings may have serious consequences personnel machinery. • The drive parameters must only be set by appropriately qualified and experienced personnel. 4.1 - General To set the MDX-I/O M2M module parame- ters, the corresponding menu is menu 19.
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING 4.2 - Diagrams Option software version Type of option 19.02 19.01 • Digital I/O Destination Invert 19.32 Digital input 6 state 19.22...
Page 13
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING • Relay outputs Source 19.37 Invert 00.00 19.27 Relay state 19.17 RL3O Output relay 3 RL3C Source RL3F 19.38 Invert 00.00...
Page 14
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING • Analog inputs and output AI4 current loop AI4 signal Analog input type 4 destination 19.41 19.42 Analog input 19.45...
Page 15
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING • Clock and trigger circuits Trigger-mode 1 Holding time Clock configuration 19.74 19.75 19.08 Reset/None Holding time unit At date...
Page 16
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING • Events Event 1 Source 19.93 min, sec 19.90 Event 1 state Day of the month, 19.94 19.91 hours Months, years 19.92...
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING 4.3 - Explanation of parameters : Clock: day of month, month 19.05 Adjustment range : 01.01 to 31.12 : Type of option 19.01...
Page 18
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : Clock configuration 19.08 : DO3 reading 19.11 Adjustment range : Time reading (0), Preparing time setting (1), Adjustment range : Inactive (0) or Active (1)
Page 19
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : Digital input 9 invert 19.25 : Output relay 4 state 19.18 Adjustment range : No (0) or Yes (1)
Page 20
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : Output relay 3 source : DO2 digital output source 19.30 19.37 Adjustment range : 00.00 to 21.51 : Output relay 4 source : 00.00...
Page 21
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : AI4 signal type : Analog input AI4 inversion 19.41 19.44 Adjustment range : 0-20 mA (0), 20-0 mA (1),...
Page 22
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : AI5 signal type : Analog input 5 destination 19.48 19.52 Adjustment range : 0-20 mA (0), 20-0 mA (1), Adjustment range : 00.00 to 21.51...
Page 23
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : Analog output 2 filter : Web server activation 19.56 19.58 Adjustment range : None (0), 4 ms (1), 8 ms (2), Adjustment range : No (0) or Yes (1) 16 ms (3), 32 ms (4).
Page 24
When one of these parameters changes from 0 to 1, the corresponding email is sent. To define the email parameters, go to the MDX-I/O M2M module web pages and configure a valid source email address, a valid destination address, the email subject and also the text. You also need to...
Page 25
W gtw .X gtw .Y gtw .Z gtw. Format : 32-bit If DHCP is enabled (see 19.61 = 1), this This parameter defines the MDX-I/O M2M address is entered automatically by the DHCP module's IP address in the format Wip.Xip. server.
Page 26
Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : Trigger-Mode 1 : MDX-I/O module reset 19.69 19.74 Reserved. Adjustment range : Reset/None (0), At date (1), Hourly (2), Daily (3), Monthly (4), : Trigger state n°1...
Page 27
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : Trigger 1 holding time 19.75 : Trigger state n°2 19.80 Adjustment range : 00 to 59 Factory setting : 00...
Page 28
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : Trigger 2 holding time : Trigger-Mode 2 19.84 19.85 Adjustment range : 00 to 59 Adjustment range : Reset/None (0),...
Page 29
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING Single (2): : Datalogger 19.88 Storage of selected variables stops as soon Adjustment range : Stop (0), Run (1), Single (2) as the trigger conditions are fulfilled.
Page 30
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : Not used : Event source 1 19.89 19.93 Adjustment range : 00.00 to 21.51 : 00.00 Factory setting : Event 1: minute, second 19.90...
Page 31
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function COMMISSIONING : Event 2: day of the month, hours : Event 2 state 19.96 19.99 Adjustment range : Inactive (0) or Active (1) Adjustment range : 01.00 to 31.23...
POWERDRIVE parameters. These can be stored continuously or triggered on configurable conditions. Data files in .csv format are stored on a 4 GB SD memory card supplied with the MDX-I/O M2M option. 5.2 - Characteristics...
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function DATALOGGER FUNCTION 5.3 - Storage configuration and trigger conditions - Insert the 4 GB memory card supplied with the drive in the PC SD port.
For more information about parameter 19.88, see section 4.3: Explanation of parameters. 5.5 - Datalogger function status LED This LED, situated on the top right of the MDX-I/O M2M card, gives the user an indication of the status of the Datalogger function.
Communication problem between the drive and the Check the MDX-I/O M2M mounting MDX-I/O link MDX-I/O M2M The 24V load current is too Check the MDX-I/O M2M option I/O MDX-I/O 24V high wiring overload Loss of the current reference Check the wiring and input source of...
3 - Using a Torx screwdriver, undo and remove the final screw in the centre of the electronic The MDX-I/O M2M module incorporates a 3 V, board and then remove the board from the Ø 16 mm lithium battery (type BR1632) to casing and turn it over.
Page 37
LEROY-SOMER Installation and commissioning manual 5146 en - 2014.03 / a MDX-I/O M2M Additional Input/Output module with Datalogger function MAINTENANCE 5 - Replace the electronic board in the casing (components facing inside the board) 6 - Then follow the same procedure in reverse to re-fit the electronic board inside its casing.