RFGate
2.1
Wireless signal transmission system for safety edges
Translation of original operating instructions
General
50.8
10.8
1

Safety instructions

Warning: Switch off the operating voltage before working on the
system. Only trained, qualified personnel may perform installation
and startup. The unit may only be repaired by the manufacturer. The
switching unit may only be used to protect against dangers on
crushing and shearing points and on automatic industrial doors and
gates (intended use). National and international regulations on
industrial door and gate safety must be complied with. Always
2

Common application

2.1
Site entrance gate
Up to 10 transmitters can be linked with
i
i
the same receiver
Transmitter
Safety edges
8.2kΩ
50.8
10.8
consider the safety functions of your application as a whole, never just in
relation to one individual section of the system. The installer is responsible
for carrying out a risk assessment and installing the industrial door system
correctly.
Receiver
50.8
It is recommended to change the batteries every year.
i
Transmitters and receivers (also among each others) must be at
i
least 0.5 m apart.
Safety edges
10.8
Transmitter
290260G
10/18
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RFGate 2.2.S and is the answer not in the manual?

Questions and answers

Summary of Contents for BBC Bircher RFGate 2.2.S

  • Page 1 290260G 10/18 RFGate Wireless signal transmission system for safety edges Translation of original operating instructions General Transmitter Receiver 50.8 50.8 50.8 10.8 10.8 10.8 Safety instructions Warning: Switch off the operating voltage before working on the consider the safety functions of your application as a whole, never just in system.
  • Page 2 Transmitter DIP switch setting according to sensor (safety edge, switch contact) RFGate 2.2.S RFGate 2.2.S.F DIP switch Sensor connection DIP switch Sensor connection DIP switch Sensor connection DIP switch Sensor connection Change from NC to NO, see chapter 3.2 IN2 has no function...
  • Page 3 Start-up Check DIP Install and wire Turn on power switch settings receiver supply Transmitters and receivers (also Transmitter: Programming (Chapter 6.1): among each others) must be at pair transmitter with receiver insert least 0.5 m apart. batteries Observe order Please observe the torque when Transmitter: Transmitter: fastening the cover:...
  • Page 4 Devices with this symbol must be treated separately during disposal. This must be done in accordance with the laws of the respective countries for environmentally sound disposal, processing and recycling of electrical and electronic equipment. Contact BBC Bircher Smart Access, BBC Bircher AG, Wiesengasse 20, CH-8222 Beringen, www.bircher.com Designed in Switzerland / Made in EU...

This manual is also suitable for:

Rfgate 2.1Rfgate 2.2.s.f

Table of Contents