Samsung AC026NNNDKH Service Manual page 9

System air conditioner, mini 4 way cassette series
Table of Contents

Advertisement

2-2 Product Specifications (cont.)
ITEM
IMAGE
OUTDOOR UNIT
REMOTE CONTROLLER
Cooling [Btu/h]
Performance
Heating [Btu/h]
Power
Consumption
Voltage / Frequency
Operating
Current
Indoor Unit [dBA] (C/H)
Noise
Outdoor Unit [dBA] (C/H)
Net Dimension
(WxHxD)
Size
Shipping
Dimension
(WxHxD)
Net Weight
Weight
Shipping
Weight
Indoor Fan Motor
Harness
Specifications
Outdoor Fan Motor
Piping
PANEL
Refrigerant Type
Factory Charging [g]
Additional Refrigerant (for every 1m) [g]
Basic Piping Length [m]
Max. Piping Length [m]
Max. Level Difference [m]
Option Code
2-4
INDOOR UNIT
Cooling [W]
Heating [W]
Cooling [A]
Heating [A]
Indoor Unit [mm]
Outdoor Unit [mm]
Indoor Unit [mm]
Outdoor Unit [mm]
Indoor Unit [kg]
Outdoor Unit [kg]
Indoor Unit [kg]
Outdoor Unit [kg]
Compressor
High Pressure
Low Pressure
Development Model
AC071NNNDKH
AC071MXADKH
6,800
7,500
2,720
2,800
1Φ, 220~240V, 50Hz
11.8
12.3
46/46
60/60
575*575*250
880*310*798
623*653*298
1023*413*911
11.4
43.8
13.7
47.5
DB31-00578C
UG4T200FUAE4
DB31-00658D
4.1
1.4
PC4SUFMAN
R-410A
1,500
20
5
50
30
01507F-194581-274750-370040
020000-100031-200000-300000
030000-100000-200000-300000
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents
loading