Wiring; Configuration - dehn DRC SCM XT Quick Start Manual

Surge protection
Table of Contents

Advertisement

Available languages

Available languages

Quick Guide
DEHNrecord DRC SCM XT

4. Wiring

Remote signalling contact (FM)
Galvanically isolated switch contact
integrated in the DRC SCM XT
monitoring module
max. 350 V d.c. / 120 mA
250 V a.c. / 70 mA
Pin: 21-22 break contact (nc)
*) switch contact shown in its normal state (all monitored SPDs are OK), that is supply
voltage is applied and the DRC SCM XT module is plugged in.
Observe the technical data of the remote signalling contact (see also 10.)!
max. 0.4 Nm
3.5 in-Ibs
Note on use in Ex (i) circuits:
Single-core, non-sheathed cables of intrinsically and non-intrinsically safe circuits routed together in conductor bundles or cable
ducts must be separated by an intermediate layer of insulating material or an earthed metal intermediate layer in accordance
with EN 60079-14. Separation is not required if sheathed cables or cable shields are used in intrinsically and non-intrinsically
safe circuits.
5. Configuration
The module must be
removed for configuration!
Decimal
Binary code
Value
8
4
2
1
0
0
0
2
0
0
1
3
0
0
1
4
0
1
0
5
0
1
0
6
0
1
1
7
0
1
1
8
1
0
0
9
1
0
0
1 0
1
0
1
22
*)
21
size 0
10*
Decimal
1 0 1 0
Binary
DIP switch
0 = Off
1
1 = On
1
8 4 2 1
0
1
0
1
0
1
0
1
0
-/+ d.c.
+/- d.c.
max. 2.5 mm²
AWG 14
Select number of
SPDs to be monitored
(max. 10)
*) example
Voltage supply
U
18...48 V d.c.; max. 100 mA
N
Pin: +/-; -/+
Recommendation DEHN:
power sypply unit
PSU DC24 30W (Part No. 910 499)
Attach label for preset
SCM address (BA1)
DEHNrecord
DRC SCM XT
Page 4