Network relay Module INstallatIoN INstructIoNs
TT-NRM-BASE
unit with four
TT-NRM-2RO
modules removed
AppROvALS
KIT cONTENTS
TT-NRM-BASE:
1
Network processor (marked 750-315)
1
24 Vdc power supply (marked 5101-7663)
1
Relay output module (marked 750-517)
1
End termination module (marked 750-600)
1
RS-485 network connection module
1
Ribbon cable with screws
1
DIN 35 rail for mounting
1
Ground terminal
2
DIN rail end stops
WARNING:
This component is an electrical device. It must be installed
correctly to ensure proper operation and to prevent shock or fire.
Read and carefully follow these important installation instructions.
THERMAL MANAGEMENT SOLUTIONS
TT-NRM
EN-TraceTekTTNRM-IM-H57474      01/13
DEScRIpTION
The TraceTek Network Relay Module provides multiple relay
outputs for switching alarm or control devices for the leak detection
system. TT-NRM units are modular and may be configured with 2 to
32 relay outputs. A single TTDM-128 unit communicates with up to
up to 20 NRMs over a single, twisted pair RS-485 cable.
ADDITIONAL MATERIALS REqUIRED
• TT-NRM-2RO, 2-channel relay output module (marked 750-517)
[up to 15 additional modules may be added to one TT-NRM-BASE]
• RS-485 cable, 1 shielded twisted pair [TT-RS485-BULK or
equivalent]
• Suitable enclosure or panel
• Additional wire, as necessary
TOOLS REqUIRED
• 3.5-mm flat-blade terminal screwdriver
• Wire stripper/cutter
REfERENcE DOcUMENTS
• TTDM-128 Installation Manual (H57341)
• TTDM-128 User Manual (H56583)

SpEcIfIcATIONS

Function
Provides relay outputs to switch power to
contactors under control of the TTDM-128
Ambient operating range 0°C to 55°C (32°F to 130°F)
Ambient storage range
–40°C to 60°C (–40°F to 140°F)
Relative humidity
5% to 95%, noncondensing
Supply voltage
94-264 Vac
Supply current
60 VA max.
Relay output type
Mechanical, normally open, voltage free
Relay output rating
230 Vac, 30 Vdc, 2 A max.
Communications
RS-485, single shielded twisted pair,
max. 20 NRM units per network
Connection terminals
28–12 AWG (0.08–2.5 mm
)
2
1 / 8

Advertisement

loading

Summary of Contents for Pentair TraceTek TT-NRM Series

  • Page 1: Specifications

    TT-NRM Network relay Module INstallatIoN INstructIoNs DEScRIpTION The TraceTek Network Relay Module provides multiple relay TT-NRM-BASE outputs for switching alarm or control devices for the leak detection unit with four system. TT-NRM units are modular and may be configured with 2 to TT-NRM-2RO 32 relay outputs.
  • Page 2 TT-NRM System Layout • The TTDM-128 controls up to 127 circuits of leak detection. TT-NRM units switch external alarm or control devices. NRMs are connected to the TTDM-128 unit via a single RS-485 network. TTDM 128 TT-NRM TT-NRM Assembly Network processor (marked 750-315) 2-channel relay output module(s) (marked 750-517) [up to 16 total m odules allowed per processor] End termination module (marked 750-600) DIN 35 rail Address switches RS-485 ribbon cable RS-485 network connection module 24 Vdc power supply ...
  • Page 3 Overview of installation procedures for TT-NRM A. Mount TT-NRM assembly in enclosure selected for the application. B. Connect power and relay contact wiring. C. Connect RS-485 cables and set address. D. Update the TTDM-128 network. A. Mount DIN rail 1. Select a location for installation. 2.
  • Page 4 B. Install TT-NRM assembly 1. Attach the TT-NRM components to the DIN rail The TT-NRM-BASE comes assembled. To remove a module, pull up on the orange release tab until the mod- ule releases from the DIN rail. Do not remove modules while power is on. Orange tab To install additional TT-NRM-2RO relay modules, you must first remove the End termination module (3) and the adjacent DIN rail end stop. Slide the additional...
  • Page 5 c. connect power wiring ® Note: TT-NRM units use WAGO cage-clamp spring terminals for secure wire connections. Using WAGO Terminals Review the steps at right for using this type of     terminal. Note: Strip length for wires in WAGO terminals is 10 mm (3/8 in). Insert flat-blade Rotate and push Insert stripped Remove screw- screwdriver into the screwdriver wire into round...
  • Page 6 3. connect wiring to relay contacts. Connect the external alarm or control devices to the terminals on each TT-NRM-2RO 2-channel relay output modules as shown. Up to 16 TT-NRM-2RO's per network processor 01 02 15 16 15 16 Status Status relay 1 relay 2 – 24V 0V POWER SUPPLY IO/RN IO/ER Common Common Address x 1 x 10 750-517 750-517 750-600...
  • Page 7 D. connect RS-485 cables and set address 1. Select the RS-485 address for the TT-NRM unit. Note: TraceTek TTSIM modules are connected on the same Each TT-NRM connected to a TTDM-128 must have a unique RS-485 network and must not have the same address as any address in the range 1 to 99. If two TT-NRM units are as- TT-NRM.
  • Page 8 Fax: +1.650.474.7215 thermal.info@pentair.com Pentair and TraceTek are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. © 2003-2013 Pentair. THERMAL MANAGEMENT SOLUTIONS EN-TraceTekTTNRM-IM-H57474      01/13...

This manual is also suitable for:

Tracetek tt-nrm-baseTracetek ttdm-128Tracetek tt-nrm-2ro