Sensible Heating Mode; Ventilation Only Mode - Trane DX Application Manual

Outdoor air unit
Hide thumbs Also See for DX:
Table of Contents

Advertisement

SYS-APG001A-EN

Sensible heating mode

If the outdoor air dew point is lower than, or equal to, the Dehumidification
Enable Setpoint, and the outdoor air dry-bulb temperature is lower than the
Heating Enable Setpoint, the unit operates in the Sensible Heating Mode
(Figure 12). In this mode, heater capacity is staged/modulated to warm the
outdoor air (OA) to the desired leaving-air dry-bulb temperature (CA).
Figure 12. Sensible heating mode
45
40
35
30
OA
30
35
40
45

Ventilation only mode

If the outdoor air dew point is lower than, or equal to, the Dehumidification
Enable Setpoint, and the outdoor air dry-bulb temperature is lower than the
Cooling Enable Setpoint but warmer than the Heating Enable Setpoint, the
unit operates in the Ventilation Only Mode. In this mode, the fan continues to
operate, but both the compressors and heater are turned off.
Dedicated Outdoor Air Systems: Trane DX Outdoor Air Unit
Control of the Dedicated OA Unit
85
sensible cooling
80
75
70
65
60
55
CA
55
60
65
70
75
80
85
dry-bulb temperature, °F