InBin-P-100
Using the menu 1 „Preset"
To beware complexity during the parametrisation process, the InBin-P has several predefined
setups which distinguish between its intended application.
You'll find a detailed desciption of all possible presets in the following section.
Fan speed monitoring
The preset „FAN" is designed for use in fan speed monitoring applications.
Menu1: Select "FAN" and press the
enter button.
If the „FAN"-preset has been selected in menu 1, all settings were made as the
following ones:
state
output
switch 1
red
state
output
switch 2
(optional)
red
The user has not to set the menu 5 „hysteresis" and menu 6 „mode", this will be done via
software. These menus will be skipped during the further parametrisation process.

Filter monitoring

The preset „FILT" is designed for use in filter monitoring applications.
Menu1: Select „FILT" and press the
enter button.
If the „FILT"-preset has been selected in menu 1, all settings were made as the following
ones:
normal
state
green
output
switch 1
normal
state
green
output
switch 2
(optional)
The user has not to set the menu 5 „hysteresis" and menu 6 „mode", this will be done via
software. These menus will be skipped during the further parametrisation process.
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
ventilator
air flow
setpoint 2
setpoint 1
Filter
Air flow
setpoint 2
setpoint 1
www.schischek.com

Professional mode

For all other applications the professional mode is designed for.
If the „PRO"-preset has been selected in menu 1, the parametrisation procedure will be
added by two further menus: menu 5 „hysteresis" and menu 6 „mode". For this preset the
user has to select the values for the hysteresis and for the mode.
Using the menu 6 „mode"
First of all the user has to define the device normal range. For example:
- The device should indicate (green LED) if the pressure is under the setpoints, mode
„down-range" has to be selected. With other words: the measure value is normally
under the setpoints.
- The device should indicate (green LED) if the pressure is over the setpoints, mode
„up-range" has to be selected. (The measure value is normally over the setpoints.)
- The device should indicate (green LED) if the pressure is between the setpoints, mode
normal
„mid-range" has to be selected. (The measure value is normally between the
green
setpoints). This mode is only for 2-stage devices available (InBin-P...-2).
In the second step the switching characteristic of the output relay has to be selected:
- „normally closed" (nc): if the measure value is in the normal range (see above), the
corresponding relays were closed.
normal
- „normally open" (no): if the measure value is in the normal range (see above), the
green
corresponding relays were open.
You'll find a detailed desciption of all possible settings in the following section.
Switching characteristic „up-range" – „normally closed"
„Up-range": the normal range is above setpoint 1 and setpoint 2
state
output
switch 1
state
output
switch 2
(optional)
red
red
E X P L O S I O N P R O O F
Menu1: Select „PRO" and press the
enter button.
setpoint 2
setpoint 1
red
red
normal
green
normal
green
D.IB-P100-02.01-en
23-Aug-2012
5 / 6