Installation - Schischek InBin-P-100 Manual

Pressure switches

Advertisement

InBin-P-100
Electrical connection
InBin-P-100 switches are equipped with a 24 VAC/DC power supply. The supply has to
be connected at terminal 1 (−/~) and 2 (+/~). The electrical wiring must be realized via
integrated junction box.
If supply voltage 24 VAC/DC differs from the relay voltage different or double isolated cables
must be used.The starting bypass delay can be activated by a short circuit of terminal 2
and teminal 3 (AUB). An active bypass delay is indicated with green blinking LEDs.
Attention: Do not open covers when circuits are alive !
Wiring diagram InBin-P-100
InBin-P-100
Relay output
24 VAC/DC
250 VAC 0,1 A / 220 VDC 0,1 A
+
30 VAC/DC / 0,5 A
~
~
PE
1
2
3
4
5
6
Display and buttons
Display for
programming and
indication
Push button
ENTER
Push button
for level select
Change operation-/parametrisation mode
To change from operation to parametrisation mode push the enter button
minimum 3 seconds. Back over the menu save.
Indication of data logging
A blinking unit in the display shows that data is received and the device is working.
Dimensions / drillings
Dimensions in mm
67
80
107
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
SB 1.0
If supply voltage 24 VAC/DC
differs from the relay voltage
different or double isolated
cables must be used.
PA
function normal close (nc) or
normal open (no) can be
selected via menu
for
55
66
www.schischek.com
E X P L O S I O N P R O O F
Password input
The default / delivery setup is 0000. In this configuration the password input is not activated.
To activate a password change the 4 digits into your chosen numbers (e.g. 1234) and press
Enter. Please keep your password in mind for next parameter change!
Due to a new parameter setup the password is requested.
Important information for installation and operation
A. Installation, commissioning, maintenance
The cable has to be drawn through the cable gland. After electrical connection the
cable gland must be fixed tighten. IP66 must be fulfilled. In acc. with operation InBin
switches are maintenance free. The sensors must not be opened by the customer.
For electrical connection use the internal junction box.
Attention: Before opening the internal junction box cut off the power supply.
B. Supply and Contact
Wires from safety extra low voltage must be separated from others. Only at 24 VAC/DC
supply and signal wires in one cable is permitted. All others use separate or double
isolated cables. Install overload protection fuse < 10 A.
C. Pressure sensors
After mounting and installation, a zero point compensation must be done, because
the offset value depends on the installation position. Have a look at parametrisation.
D. Long cabling
For using long signal wires, shielded cables are recommended. The shield must be
connected to the InBin-P switch inside the terminal box.
E. Separate ground wires
Use for supply and signal wires a separate ground.

Installation

Safe area
P+ P−
▪ Maintenance must comply with regional standards, rules and regulations
▪ Do not open covers when circuits are alive
▪ For electrical connection use the integrated junction box
▪ The cable must be installed in a fixed position and protected against mechanical
and thermical damage
▪ Connect protection earth
▪ Avoid thermal transfer from sensor probe to transducer (ensure max. ambient temperature).
▪ Ambient temperature −20...+50 °C
▪ Close all covers, entries with min. IP66
▪ All transducers are maintenance free
▪ For outdoor installation a protective housing against rain, snow and sun should be applied
▪ Only wet cleaning
Zero point compensation for pressure transmitter
For a InBin-P-100 pressure switch installation a zero point compensation should be
performed to adjust value deviations of the module's installation position. Therefore the
pressure nipples P+ / P− must be connected with a short circuit tube and the zero point
compensation accomplished by following the menu.
Before starting the compensation the device should be connected to the power supply for
minimum of 15 minutes to reach the working temperature!
Supply
24 VAC/DC
Relay output
250 VAC/0,1 A 30 V/0,5 A
D.IB-P100-02.01-en
23-Aug-2012
3 / 6