4°) Connect back
the ribbon cable and close
the cabinet
4
START-UP – TESTS
As soon as the alarm unit is powered, it begins a test of its alarming devices (LED and buzzer).
l
Test of all sensors connection (short circuit and broken cable of measuring loops).
l
Detection of sensor type, if the result is positive, the corresponding LED will light on.
In case of a defect detected, the 3 LED, corresponding to this input, will be flashing.
For a non connected channel, the 3 LED keep OFF.
During the first start-up, the alarm device NivOil memorizes the type of sensor connected
to each chan-nel.
l
When the TEST mode is activated, an audible signal occurs if everything is correct.
The factory settings are: "without sensors"
l
When you connect a new sensor on a free channel, the alarm device NivOil will identify and
memorize it as soon as you switch on the power.
If a sensor is removed, the corresponding 3 LED will be flashing (defect alarm).
Proceed to a reset, pressing the RESET button at least 5 seconds to confirm the removal of the
sensor.
l
When a sensor is removed without a complete RESET, then all the LED will be flashing to alarm
of this error status.