Download Print this page

Bamo NivOil Instruction Manual page 5

12v dc alarm system for oil-water separators
Hide thumbs Also See for NivOil:

Advertisement

Monitoring modes: continuous monitoring, cyclic monitoring
The energy consumption is adjustable by modifying the duration of each monitoring cycle through
the settings of the DIP switch and the selector. The monitoring frequency is adjustable from 6
minutes to 9 days. Between 2 monitoring, the alarm unit is in sleep mode (monitoring function
in stand by).
When there is not a specific sleep mode period (selector on "0" and DIP 6, 7 and 8 are in ON
position), the alarm unit is continuously monitoring.
When the cyclic monitoring mode is set up, each monitoring cycle begins with a self-diagnostic
of sensors and detection loops in order to begin an alarm routine if necessary.
With 3 sensors connected to the alarm unit, a survey monitoring is completed in about 90 seconds.
The progress of each cycle is shown through a blinking LED (each 4 seconds approx.) on the
front panel.
During the sleep mode period, by pressing the TEST button (1 second approx.) it is possible to
begin directly a monitoring sequence:
l
At this moment, the alarm unit begins its self-diagnostic
l
In case of an alarm condition detected, it begins an alarm routine.
l
After 90 seconds, the system goes back to the previous cyclic mode.
2°) Preparing the cables: Remove the external sheath as on the picture A and fit on a cable ter-
minal ends
Cable extension
The maximal length of an extension is 300 m.
Use the specific cable reference SK-PVC-2x1, ATEX certified.
The easier way to extend the cable accordingly with ATEX rules, is to use the CET02 cable
coupling (Pic.B), reference NivOil-JT, suitable to ATEX zone 0 category 1.
The device is delivered with 2 WAGO connectors (Pic. C) for fast coupling.
Pic. A
Cable cross section: 4 mm
Protection: IP 65 (not for a continuous immersion)
The shield must not be connected.
Both ends must be pressed to the limit and pressure cable glands well tightened.
3°) Connect the sensors to the control unit NivOil in accordance with the obligations due to Ex
area, as shown on the drawing.
The measuring loop, as an intrinsic safe circuit, must not be connected to the ground.
Connect the control unit to the main power line.
531 M1 02 A
16-07-2010
_________________________
2
as a maximum
Pic. B
Pic. C
5

Advertisement

loading