Panel Mounting - GE VersaMax IC200CPUE05 Manual

Table of Contents

Advertisement

CPU with Embedded Ethernet Interface
IC200CPUE05
Panel-Mounting
If excessive vibration is a factor, the CPU should also be screwed down to the mounting panel.
Note 1. Tolerances are ±0.13mm (0.005in) non-cumulative.
Note 2. 1.1-1.4Nm (10-12 in/lbs) of torque should be applied to M3.5 (#6-32) steel screw threaded into material
containing internal threads and having a minimum thickness of 2.4mm (0.093in).
Removing the CPU from the DIN Rail
1.
Turn off power to the power supply.
2.
(If the CPU is attached to the panel with a screw) remove the power supply module. Remove the panel-mount
screw.
3.
Slide the CPU away from the other modules until the connector on the right side disengages from the next carrier.
4.
With a small flathead screwdriver, pull the DIN rail latch outward while tilting the other end of the module down to
disengage it from the DIN rail.
Activating or Replacing the Backup Battery
The CPU is shipped with a battery already installed. The battery holder is located in the top side of the CPU module.
Before the first use, activate the battery by pulling and removing the insulator tab.
To replace the battery, use a small screwdriver to gently pry open the battery holder. Replace battery only withACC001
from your PLC supplier, or with Panasonic battery: BR2032. Use of another battery may present a risk of fire or
explosion.
4.3mm
0.170in
4.3mm
0.170in
5.1mm
0.200in
Battery may explode if mistreated.
Do not recharge, disassemble, heat above 100°C (212°F), or incinerate.
SEE NOTE 2.
M3.5 (#6) SCREW
SPLIT LOCK
WASHER
FLAT WASHER
15.9mm
0.62in REF
TAPPED
CPU
HOLE IN
PANEL
Caution
5
GFK-1892TW