for 4041-5300 Temptrace™ Universal Kit for
Self-Regulating Bundles
Bulletin S/T-II
Temptrace™ 4041-5300 Electrical Splice or Tee Connection Kit for
SL & SH Series Self-Regulating Bundles
Scope
Kit can be used to make one input power connection or one input power splice connection or one splice/tee
connection as well as two end termination and RTV for bundle end seal.
An easily installed combination power splice and tee for Self-Regulating Bundle.
Bill of Materials
(1) 3/4" Pipe Stand
(1) 3/4" Pipe Nipple
(2) Sealing Grommet
(4) Stainless Steel Pipe Straps
(2-large, 2-small)
(1) 3 Hub Box
(1) Box Cover
(6) Wire Nuts
(2) Butt Splice Connectors
(1) SK-612 (Seal Patch Kit)
(3) Sleeve Rubber Heating Cable
Boot
Caution: The heater will come in contact with the power feed wires in the
junction box. Make sure that the temperature rating of the power feed wire
insulation is adequate for the heater used.
Ground Fault Equipment Protection Devices (GFEPDs):
The IEEE standard (515-2004) for heating cables requires the use of GFEPDs
with a nominal 30 milliampere trip level for "piping systems in classified areas,
those areas requiring a high degree of maintenance, or which may be exposed
to physical abuse or corrosive atmospheres."
(3) Ring Terminals
(2) Cable Entry Fittings
(1) 3/4" Pipe Plug
(1) Grounding Screw
(2) RTV-103BLK
(1) SS Label
(2) Reducing Bushings
(3) 1" Heat Shrink Tubes
(3) 3" Heat Shrink Tubes
(1) 4041-5300 Installation
instructions
(1) Fiberglass tape GT-3
Contact Information:
Parker Hannifin Corporation
Parflex Division
1300 N. Freedom St.
Ravenna, OH 44266 USA
phone 330 296 2871
fax 330 296 0675
www.parker.com/pfd

Advertisement

loading
Need help?

Need help?

Do you have a question about the Temptrace SL Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Parker Temptrace SL Series

  • Page 1 Contact Information: Technical Data Sheet & Installation Instructions Parker Hannifin Corporation Parflex Division for 4041-5300 Temptrace™ Universal Kit for 1300 N. Freedom St. Ravenna, OH 44266 USA Self-Regulating Bundles phone 330 296 2871 Bulletin S/T-II fax 330 296 0675 www.parker.com/pfd Temptrace™...
  • Page 2 If an HSB (heat shrinkable boot) or ESB (end seal boot) is used to seal the end of the bundle, the boot must be installed prior to installing the base of the heating cable. Parker Hannifin Corporation Parflex Division Ravenna, OH USA www.parker.com/pfd...
  • Page 3 RTV can also be used. Use appropriate tube fitting avail- Slide the seal grommet over the able from Parker Instrumentation heating cable and position the Connectors Division. grommet in the standoff. Note: If heater wire is braided...
  • Page 4 SK-612 Tube fittings are available from Please follow steps 1-8 in “Instructions for Splice or Tee Connections,” except use a Tee union fitting available from your local Parker Instrumentation Distributor to bring your local Parker Instrumentation Distributor. in an additional bundle. Utilize top port of junction box with splice or Tee connection.
  • Page 5 Typical Power Connection occur. HSB or RTV-103BLK sealant Fitting used in connection can be obtained from your local Parker Instrumentation Distributor. Parker Hannifin Corporation Parflex Division Ravenna, OH USA www.parker.com/pfd...
  • Page 6 Pull the braid tight. Lightly cut the jacket up the center to the end of heating cable and peal away that section. Shave the core material from outside of each bus wire. Parker Hannifin Corporation Parflex Division Ravenna, OH USA www.parker.com/pfd...
  • Page 7 Heat until tube shrinks tube is still hot, pinch end of tube around cable. Using pliers, while to seal. tube is still hot, pinch end of tube to seal. Parker Hannifin Corporation Parflex Division Ravenna, OH USA www.parker.com/pfd...
  • Page 8 © 2014-2018 Parker Hannifin Corporation Bulletin S/T-II 8/2018...

This manual is also suitable for:

Temptrace sh seriesTemptrace 4041Temptrace 5300