7.3 Adjusting the electrode plugs (see sketch page 9)
If insertion of the electrode plugs (2) is not possible because of the position of
the contact carrier (4), take the following steps:
Keep releasing the threaded ring (5) until the contact carrier (4) can be lifted.
• Turn the contact carrier (4) into the required position and snap in;
retighten the electrode plug (5).
7.4 Shortening the electrode extension (see sketch page 9)
Never dismantle the electrode when the boiler / mounting housing is
pressurised!
Release screw (1) and pull off electrode plug (2).
Screw out electrode.
Dismount electrode extension (9) by screwing out the set screw.
Clamp electrode extension (9) directly at the point to be shortened and
shorten. Do not distort the electrode extension!
Lengthening is not permissible!
Do not heat insulate electrode head - all parts above the thread (7)!!