Main Electrical Power; Requirements; Low Voltage Wiring (Ac & Dc); Field Installed Power Wiring - Trane Axiom GWS Series Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

I I n n s s t t a a l l l l a a t t i i o o n n
1 through 3 and go on to next step in the installation
process.
Table 4. TCO-A replaced for horizontal duct
configuration
Unit Model
Electric Heater
Number
Model Number
GWSC092H3
BAYHTRU336
GWSC092H4
BAYHTRU436
GWSC120H4
BAYHTRA454
BAYHTRAW36, W54
GWSC120HW
BAYHTRW327, 336
GWSC072H3
BAYHTRU427, 436
GWSC072H4
BAYHTRWW27,
GWSC072HW
1. Remove the heater section access panel and open
the electric heater dead front panel.
2. TCO-A is the limit control located in the central or
right part of the heater mounting plate and that is
located on the bottom of the two heater element
assemblies. To replace this device, first remove the
two wires connected to the terminals. Next, remove
the two screws which secure it to the heater
element mounting plate. Once TCO-A has been
removed from the heater element mounting plate,
discard this device.
Figure 41. TCO-A location
38
TCO-A location
Center
Center
Right
Right
Center
Center
Center
W36
3. Obtain the replacement TCO-A which is secured by
a wire tie near the electric heater terminal block in
the heater compartment. Attach it to the heater
element mounting plate with the two screws that
were removed in step 2 above. Connect the two
wires that were un-hooked in step 2 to the terminals
on the new TCO-A. Refer to the heater package
wiring diagram to assure that the wiring is
connected properly.
4. Close the electric heater dead front panel and
replace heat section access panel.
Electrical Requirements
W W A A R R N N I I N N G G
P P r r o o p p e e r r F F i i e e l l d d W W i i r r i i n n g g a a n n d d G G r r o o u u n n d d i i n n g g
R R e e q q u u i i r r e e d d ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w c c o o d d e e c c o o u u l l d d r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r
s s e e r r i i o o u u s s i i n n j j u u r r y y . .
A A l l l l f f i i e e l l d d w w i i r r i i n n g g M M U U S S T T b b e e p p e e r r f f o o r r m m e e d d b b y y q q u u a a l l i i f f i i e e d d
p p e e r r s s o o n n n n e e l l . . I I m m p p r r o o p p e e r r l l y y i i n n s s t t a a l l l l e e d d a a n n d d g g r r o o u u n n d d e e d d
f f i i e e l l d d w w i i r r i i n n g g p p o o s s e e s s F F I I R R E E a a n n d d E E L L E E C C T T R R O O C C U U T T I I O O N N
h h a a z z a a r r d d s s . . T T o o a a v v o o i i d d t t h h e e s s e e h h a a z z a a r r d d s s , , y y o o u u M M U U S S T T f f o o l l l l o o w w
r r e e q q u u i i r r e e m m e e n n t t s s f f o o r r f f i i e e l l d d w w i i r r i i n n g g i i n n s s t t a a l l l l a a t t i i o o n n a a n n d d
g g r r o o u u n n d d i i n n g g a a s s d d e e s s c c r r i i b b e e d d i i n n N N E E C C a a n n d d y y o o u u r r l l o o c c a a l l / /
s s t t a a t t e e / / n n a a t t i i o o n n a a l l e e l l e e c c t t r r i i c c a a l l c c o o d d e e s s . .
Main Electrical Power Requirements
Verify that the power supply complies with the unit
nameplate specifications.
Inspect all control panel components; tighten any
loose connections.
Connect properly sized and protected power supply
wiring to a field-supplied/installed disconnect
switch and to the main power terminal block (HTB1)
in the unit control panel.
Install proper grounding wires to an earth ground.
N N o o t t e e : : All field-installed wiring must comply with NEC
and applicable local codes.
Low Voltage Wiring (AC & DC)

Requirements

Install the zone thermostat, with or without
switching subbase.
Connect properly sized control wiring to the proper
termination points between the zone thermostat
and the unit control panel.

Field Installed Power Wiring

An overall dimensional layout for the standard field
installed wiring entrance into the unit is illustrated in
the
"Unit Dimensions," p. 14
unit's supply power wiring is properly sized and
installed, follow the guidelines outlined below.
section. To insure that the
WSHP-SVX015C-EN